Setting the parameter unit and operation panel
4.22.3 Operation panel frequency setting/key lock operation selection (Pr. 161)
The above parameter can be set when Pr. 160 Extended function display selection = "0". (Refer to page 162)
(1) Using the setting dial like a potentiometer to set the frequency
The setting dial of the operation panel can be used for setting like a potentiometer.
The key operation of the operation panel can be disabled.
Parameter 
Number
Name
Initial Value
Setting 
Range
Description
161
Frequency setting/key lock 
operation selection
0
0
Setting dial frequency 
setting mode
Key lock invalid
1
Setting dial
 potentiometer mode
10
Setting dial frequency 
setting mode
Key lock valid
11
Setting dial
 potentiometer mode
Operation example Changing the frequency from 0Hz to 60Hz during operation
Operation Display 
1.
Screen at powering on
The monitor display appears.
2.
Press 
to choose the PU operation mode.
PU indication is lit.
3.
Press 
 to choose the parameter setting 
mode.
PRM indication is lit.
(The parameter number read previously
appears.)
4.
Turn  
until 
 
(Pr. 160) appears.
5.
Press
 to read the present set value.
"
"(initial value) appears.
6.
Turn 
 to change it to the set value "
".
7.
Press
 to set.
Flicker   Parameter setting complete!!
8.
Change Pr. 161 to the setting value of "
 "
in the similar manner. (Refer to step 4 to 7.)
Flicker   Parameter setting complete!!
9.
Mode/monitor check 
Press 
 twice to choose the monitor/
frequency monitor.
10.
Press 
 to start the inverter.
11.
Turn 
 until "
" appears.
The flickering frequency is the set frequency. 
You need not press 
.
The frequency flickers for about 5s.