T7351 COMMERCIAL PROGRAMMABLE THERMOSTAT
63-2666—02
10
Holidays and 365 - Day Clock
The T7351can be configured to schedule up to 10 separate 
holidays, each with a duration of up to 99 days. To enable this 
function, the user must set the date:
1. Press Set Day and Set Time keys simultaneously.
2. Use the Up/Down keys to set the date to YES, then 
press the 
 key. 
3. Use the Up/Down keys to set the month, then press the 
 key. 
4. Use the Up/Down keys to set the day, then press the 
 
key (Refer to Table 4 for valid day choices).
5. Use the Up/Down keys to set the year, then press the 
 key. 
Holidays can be set in the following manner:
1. Press the “Temporary Occupied” and Temporary Not 
Occupied” keys simultaneously.
2. The month (MON) of the first holiday is then displayed 
(00 means the holiday is ignored).
3. Use the Up/Down keys to set the month, then press the 
 key. 
DAT HL
NO
YES or NO
Discharge High Limit (Only displayed if Discharge Air Sensor is Selected)
NO: None
YES: Enabled
DATHLSP 110° F
(43° C)
65° - 140° F
(18° - 60° C)
Discharge High Temperature Limit
(Display only if Discharge Sensor is configured)
DEHUMID 0
0 - 5
Dehumidification
0: None
1: MinOn Time
2: Reset Temp Setpoint
3: Reset w/ MinOn
4: Reheat
5: Reheat w/ Min On
DEH MIN
5
5 - 15
Dehumidify Minutes On
DEH TMP 2
1 - 5
Dehumidify Temp Reset
MINHTRT 5
0 - 20 DDF/HR Minimum Heat Recovery Ramp Rate
MAXHTRT 8
0 - 20 DDF/HR Maximum Heat Recovery Ramp Rate (Only Displayed if Outdoor Sensor is Selected)
MINHTOA 0° F
(-18° C)
-20° - 120° F
(-29° - 49° C)
Minimum Heat Outdoor Air Temperature (Only Displayed if Outdoor Sensor is Selected)
MAXHTOA 40° F
(4° C)
-20° - 120° F
(-29° - 49° C)
Maximum Heat Outdoor Air Temperature (Only Displayed if Outdoor Sensor is Selected)
MINCLRT
3
0 - 20 DDF/HR Minimum Cool Recovery Ramp Rate
MAXCLRT 6
0 - 20 DDF/HR Maximum Cool Recovery Ramp Rate (Only Displayed if Outdoor Sensor is Selected)
MINCLOA 90° F
(32° C)
-20° - 120° F
(-29° - 49° C)
Minimum Cool Outdoor Air Temperature (Only Displayed if Outdoor Sensor is Selected)
MAXCLOA 70° F
(21° C)
-20° - 120° F
(-29° - 49° C)
Maximum Cool Outdoor Air Temperature (Only Displayed if Outdoor Sensor is Selected)
(DayLight Savings options only display when Date is valid)
DSTMON1 3
0 - 12
DLS Spring Month
DSTDAY1 40
0 - 31, 32 - 74
DLS Spring Day
0 - 31 = Day of Month
32 = Last Day of Month
33 = First Sunday
etc…
DSTMON2 11
0 - 12
DLS Fall Month
DSTDAY2 33
0 - 31, 32 - 74
DLS Fall Day
0 - 31 = Day of Month
32 = Last Day of Month
33 = First Sunday
etc…
HT RESP
1
0 - 3
0: Standard - 3 cph
1: Medium - 6 cph
2: Fast - 9 cph
3: Super Fast - 20 cph
CL RESP
0
0 - 1
0: Standard - 3 cph
1: Fast - 4 cph
Table 5. Installer Setup. (Continued)
Text
Default
Choices
Notes