Special adjustment for measuring and adjusting CO2 levels
9
Special adjustment for measuring and adjusting CO
2
 levels
The CO
2
 can  only be adjusted  by  a  certified gas
technician with a calibrated CO
2
 analyzer.
9.1
Adjusting the unit
Factory settings of this appliance are listed in table 7.
Further adjustment is only needed if optimal CO
2
 level
is  required  in  order  to  assure  the  minimum  possible
CO
2
 emissions. In this case a CO
2
 analyzer is required.
9.1.1
CO
2
 measuring 
B Loosen screw 1 (Fig. 41).
B Insert  CO
2
  analyzer  into  measuring  port  (Fig.  41,
pos. 1).
Fig. 41
1
Measuring point
9.1.2
Selecting adjustment mode
B ON/OFF switch in position OFF (0).
CO
2
 adjustment at minimum gas flow (P2) - See
table 7.
B Press  “Program”  key  and  turn  ON/OFF  switch  to
position ON.
Fig. 42
LCD  shows  “P2”  and  the  appliance  is  ready  to  be
adjusted.
B Open hot water tap.
The  appliance  will  run  constantly  at  minimum  power
output and minimum water flow. This program step can
also be used to measure minimum output and minimum
water flow.
B Turn the screw in order to regulate the air-gas mixture
inside  the  ventilator  until  the  CO
2
  level  required  is
reached (Fig. 43, pos. 3).
CO
2
 adjustment at maximum gas flow (P1) - See
table 7.
B Press 
, until “P1” appears.
B Open hot water tap.
The  appliance  will  run  constantly  at  maximum  power
output and maximum water flow. This program step can
also be used to measure maximum output and maximum
water flow.
B Turn the screw in order to regulate the air-gas mixture
inside  the  ventilator  until  the  CO
2
  level  required  is
reached (Fig. 43, pos. 3).
Caution: Converting the gas type can
only  be  done  by  a  certified  gas
technician  with  a  calibrated  CO
2
analyzer.  Call  CEC  for  conversion
instructions.
Caution:  Adjustments  must  only  be
carried  out  by  authorized  service
personnel only.
Caution: The appliance should always
be disconnected from the power supply
before any maintenance is carried out.
Factory 
setting
Field settings 
acceptable range
Nat. Gas
Nat. Gas
max. input
P1
9.50 %
8.00 % to 10.00 %
min. input
P2
9.50 %
8.00 % to 10.00 %
LP Gas
LP Gas
max. input
P1
10.50 %
10.00 % to 11.00 %
min. input
P2
10.50 %
10.00 % to 11.00 %
*  Final reading  must  be confirmed  with the  front cover
on, CO
2
 levels increase when the cover is installed.
Table 7