SOLID STATE ECONOMIZER SYSTEM
63-2484—2
14
M7415 Damper Actuator
Single M7415 Damper Actuator accepts thermistor sensor 
input from a C7046A or a C7150B Mixed Air Sensor mounted 
in discharge or mixed air duct. See Fig. 27. 
During the occupied period, on a call for cooling, when outdoor 
air temperature or enthalpy conditions are low, the M7415 
Actuator proportions to maintain between 50°F (10°C) and 
56°F (13°C) at the thermistor sensor. 
If the mixed or discharge temperature is above 56°F (13°C), 
the M7415 Actuator opens to admit additional outdoor air until 
the temperature returns to the 50°F (10°C) to 56°F (13°C) 
range. If the mixed or discharge air temperature is below 50°F 
(10°C), the actuator proportions closed, shutting the outdoor 
air damper until the temperature returns to the 50°F (10°C) to 
56°F (13°C) range. During the occupied period, the actuator 
does not close past the minimum position. 
If the fully open M7415 Actuator cannot satisfy the space 
demand, mechanical cooling is sequenced on. 
During the unoccupied period, the M7415 Actuator overrides 
the minimum position setting and drives fully closed. On a loss 
of power, the actuator spring-returns fully closed. 
If terminals P and P1 are jumpered, the M7415 drives fully 
open; however, if terminals P and P1 are left open, the M7415 
drives fully closed. The M7415 minimum position adjustment 
drives the motor open when the resistance across P and P1 is 
minimal. Increasing the amount of resistance across these 
terminals drives the actuator closed. 
M8405 Damper Actuator
An spst low-voltage controller is used to control the M8405 
Actuator as follows:
a. Fully open—when the controller circuit closes to pro-
vide 24 Vac to terminals D and T, the actuator is 
energized and runs fully open.
b. Fully closed—when the controller circuit opens, 
power is removed from terminals D and T, and the 
actuator spring-returns to the fully closed position.
c. Mid-position—when the controller circuit closes to 
provide 24 Vac to terminals T and X, the actuator is 
energized to run to the adjustable mid-position (mini-
mum position).
Adjustable minimum position can be reached from either the 
fully closed or fully open position. From fully closed, the 
actuator drives open to the minimum position; from fully open, 
the actuator spring-returns to minimum position.
W7459A,C Solid State Economizer Logic 
Module 
The purpose of an economizer is to use outdoor air for cooling 
whenever possible, to reduce air conditioner compressor 
operation. The W7459 Economizer System, when wired as 
shown in Fig. 27, responds to a signal from the cooling 
thermostat. This system uses a C7400 Enthalpy Sensor or a 
C7650A Temperature Sensor. It responds to both dry bulb 
temperature and humidity, allowing the use of outdoor air at 
higher temperatures for free cooling when the humidity is low. 
The economizer functions as a true first stage of cooling and 
provides maximum fuel economy during the cooling cycle. The 
economizer is automatically locked out during heating. It holds 
the outdoor air damper at the minimum position setting. On a 
call for cooling by the space thermostat, the system operates 
as follows: 
When the enthalpy or temperature of the outdoor air is below 
the setpoint, the outdoor air damper is proportioned open (and 
the return air damper is proportioned closed) to maintain 
between 50°F and 56°F (10°C and 13°C) at the mixed/ 
discharge air sensor. During economizer operation, the 
mechanical cooling is operated by stage 2 cooling on the 
space thermostat. 
When the enthalpy or temperature of the outdoor air is above 
the setpoint, the outdoor air damper closes to its minimum 
position. A call for cooling from the space thermostat turns on 
the mechanical cooling. 
During the unoccupied period, the M7415 Damper Actuator 
spring-returns the outdoor air damper to the fully closed 
position. 
W7212A Economizer Logic Module
W7212A economizer logic module used with C7400 enthalpy 
sensors, M7215 or MS7505 damper actuators and C7232 CO
2
 
sensors to proportion outdoor and return air dampers from 
economizer and demand control ventilation in commercial 
HVAC equipment.
W7212A Optional Applications
HEAT PUMP CHANGEOVER (W7213, W7214 ONLY)
In heat pump applications, the controller must have control of 
the changeover valve. To provide the logic module with the 
information necessary for proper information, there must be a 
connection to the logic module O/B terminal. This terminal 
alerts the logic module as to when the system operates in 
cooling (the only time the economizer is used).
W7213 (CHANGEOVER TERMINAL B)
Connect the B terminal according to the following details:
— 24V power to B: System is in heating mode.
— No power to B: System is in cooling mode.
W7214 (CHANGEOVER TERMINAL O)
Connect the O terminal according to the following details:
— 24V power to O: System is in cooling mode.
— No power to O: System is in heating mode.
SETTINGS AND ADJUSTMENTS
Adjusting Minimum Damper Position
The minimum position potentiometer keeps the outdoor air 
damper from completely closing during system operation to 
allow ventilation.