Honeywell RM7800G ユーザーズマニュアル

ページ / 16
RM7800E,G,L,M; RM7840E,G,L,M 7800 SERIES RELAY MODULES
66-1085—3
6
Table 4. Combinations for Terminals 8, 9, 10 and 21.
Table 5. Explanation of Each Combination.
Mounting RM7800/RM7840 
Relay Module (Fig. 5)
1.
Mount the RM7800/RM7840 vertically on the Q7800 
Subbase, or mount horizontally with the knife blade 
terminals pointing downward. When mounted on the 
Q7800A, the RM7800/RM7840 must be in an electrical 
enclosure. 
2.
When mounting in an electrical enclosure, provide 
adequate clearance for servicing, installation and 
removal of the RM7800/RM7840, Keyboard Display 
Module, flame amplifier, flame amplifier signal voltage 
probes, electrical signal voltage probes, and electrical 
connections. 
a. Allow an additional two inches below the 
RM7800/RM7840 for the flame amplifier mounting. 
b. Allow an optional three-inch minimum to both sides 
of the RM7800/RM7840 for electrical signal voltage 
probes. 
3.
Make sure no subbase wiring is projecting beyond the 
terminal blocks. Tuck in wiring against the back of the 
subbase so it does not interfere with the knife blade 
terminals or bifurcated contacts. 
IMPORTANT
The RM7800/RM7840 must be installed with a 
plug-in motion rather than a hinge action.
4.
Mount the RM7800/RM7840 by aligning the four 
L-shaped corner guides and knife blade terminals with 
the bifurcated contacts on the wiring subbase and 
securely tighten the two screws without deforming the 
plastic. 
Combination No.
Pilot Fuel 8
Main 9
Ignition 10
Intermittent Pilot Valve 21
1
C
F
No Load
No Load
2
B
F
No Load
No Load
3
No Load
F
No Load
B
4
F
F
A
No Load
5
No Load
F
A
F
6
D
F
A
No Load
7
No Load
D
A
D
8
D
D
A
No Load
9
No Load
D
A
D
A
B
C
D
F
4.5A ignition.
50 VA Pilot Duty plus 
4.5A ignition.
180 VA ignition plus 
motor valve with:
660 VA inrush, 360 VA 
open, 260 VA hold.
2A Pilot Duty.
64 VA Pilot Duty plus motor 
valves with:
3850 VA inrush, 700 VA 