Honeywell automatic vent damper d896 ユーザーズマニュアル
D896 AUTOMATIC VENT DAMPER
68-0186
3
NOTE:
A minimum of a 30 VA transformer must be used
when D896 is installed with S86/S8600/S8610/
S8620.
when D896 is installed with S86/S8600/S8610/
S8620.
Electrical Connections:
Four-wire plug receptacle.
Four-wire plug receptacle.
Thermostat Anticipator Setting:
0.13A.
0.13A.
Operating Times:
Approximate Damper Opening Time: 30 seconds.
Approximate Damper Closing Time: 30 seconds.
Approximate Damper Closing Time: 30 seconds.
Temperature Ratings:
Minimum Ambient: 32
°
F (0
°
C).
Maximum Ambient: 150
°
F (66
°
C).
Maximum Furnace Stack: 575
°
F (302
°
C).
Shipping: -20
°
F to +120
°
F (-29
°
C to +49
°
C).
Mounting: See Fig. 2.
Vertical Stack: Any orientation.
Horizontal Stack: The damper actuator must be on the left
Horizontal Stack: The damper actuator must be on the left
or right side of the vent.
IMPORTANT
Do not mount the vent damper with the actuator
above or below the vent.
above or below the vent.
Dimensions:
See Fig. 1.
DIA
A
DIA
B
DIM.
G
DIM.
H
1 (32)
1
4
4
2
3
4
4
DIA
C
4 (116)
9
16
DIM.
D
3 (98)
7
8
8
7/8 DIA. STD. KNOCKOUT (3)
(ONE, OPPOSITE SIDE)
(ONE, OPPOSITE SIDE)
4 (102)
5 (127)
6 (152)
7 (178)
8 (203)
9 (229)
10 (254)
11 (279)
12 (305)
3 15/16 (100)
4 15/16 (125)
5 15/16 (151)
6 15/16 (176)
7 15/16 (202)
8 15/16 (224)
9 15/16 (252)
10 15/16 (278)
11 15/16 (303)
1 9/16 (40)
1 9/16 (40)
1 9/16 (40)
3 3/16 (81)
3 3/16 (81)
3 3/16 (81)
5 3/16 (132)
5 3/16 (132)
5 3/16 (132)
4 1/2 (114)
4 1/2 (114)
4 1/2 (114)
7 1/2 (191)
7 1/2 (191)
7 1/2 (191)
11 1/2 (292)
11 1/2 (292)
11 1/2 (292)
4 (102)
5 (127)
6 (152)
7 (178)
8 (203)
9 (229)
10 (254)
11 (279)
12 (305)
4 1/16 (103)
5 1/16 (129)
6 1/16 (154)
7 1/16 (179)
8 1/16 (205)
9 1/16 (230)
10 1/16 (256)
11 1/16 (281)
12 1/16 (306)
6 (152)
6 (152)
6 (152)
9 (229)
9 (229)
9 (229)
13 (330)
13 (330)
13 (330)
6 3/4 (171)
7 1/4 (184)
7 3/4 (197)
8 1/4 (209)
8 3/4 (222)
9 1/4 (235)
9 3/4 (248)
10 1/4 (260)
10 3/4 (274)
8 7/8 (225)
9 7/8 (251)
10 7/8 (276)
11 7/8 (301)
12 7/8 (327)
13 7/8 (352)
14 7/8 (378)
15 7/8 (403)
16 7/8 (428)
M11381
DIM. F
DIM. E
(70)
BODY SIZE
(REF)
DIA. A
in. (mm)
DIA. B
in. (mm)
DIA. C
in. (mm)
DIM. D
in. (mm)
DIM. E
in. (mm)
DIM. F
in. (mm)
DIM. G
in. (mm)
DIM. H
in. (mm)
Approvals:
American Gas Association Certified:
Certificate No. U-66-2A1.
Canadian Gas Association Design Certified:
1029AVD-9081.
Replacement Parts:
Damper Actuator is field replaceable without removing the
damper assembly from the stack.
197516A Wiring Harness is a 4-wire cable, 8 feet (2.5
meters) long, with D896 mating plug on one end and
mating plug for S86/S8600/S8610/S8620 or Penn Baso
G60 or G66 on the other. An outlet box connector is on
each end.
mating plug for S86/S8600/S8610/S8620 or Penn Baso
G60 or G66 on the other. An outlet box connector is on
each end.
APPLICATION
The D896 Automatic Vent Damper is a 24 Vac, motorized
stack damper. The damper closes off the furnace or boiler
stack during the heating off-cycle. Use the D896 only on
Underwriters Laboratories Inc. listed and American Gas
Association design certified atmospheric type, gas-fired
furnaces and boilers. The furnaces or boilers must be
equipped with a draft hood that has an outlet area no larger
than the damper inlet area. Do
stack damper. The damper closes off the furnace or boiler
stack during the heating off-cycle. Use the D896 only on
Underwriters Laboratories Inc. listed and American Gas
Association design certified atmospheric type, gas-fired
furnaces and boilers. The furnaces or boilers must be
equipped with a draft hood that has an outlet area no larger
than the damper inlet area. Do
not use with oil-fired furnace
or boiler, power burner, or direct vent furnace or boiler.
Fig. 1. Installation dimensions in in. (mm).