L4188A,B; L4189A,B; L6188A-C; L6189A-C AQUASTAT® CONTROLLERS
68-0061—1
4
Accessories (order separately): 
Capillary compression fittings.
Part No. 104484A: 1/2 in. NPT spud.
Part No. 104484B: 3/4 in. NPT spud.
Immersion well: Pressure rating 255 psi [1760 kPa].
Part No. 45900409-003B: 1/2 in. BSPT spud, 1 in. 
insulation, 3-1/2 in. insertion.
Part No. 45900409-009B: 1/2 in. NPT spud, 1-1/2 in. 
insulation, 3 in. insertion.
Part No. 45900409-010B: 3/4 in. NPT spud, 1-1/2 in. 
insulation, 3 in. insertion.
Optional Specifications (Specify when ordering): 
• Combination screw and 1/4 in. male quick-connect 
terminals.
• High or low limit stop (models with knob only).
• Mounting bracket (remote bulb models only).
INSTALLATION
When Installing This Product...
1. Read these instructions carefully. Failure to follow them 
could damage the product or cause a hazardous 
condition.
2. Check the ratings given in the instructions and on the 
product to make sure the product is suitable for your 
application.
3. Installer must be a trained, experienced service 
technician.
4. After installation is complete, check out product 
operation as provided in these instructions.
CAUTION
Disconnect power supply before wiring to avoid 
electrical shock or equipment damage.
Terminal connections must be inside an enclosure 
that meets local electrical codes.
Location
The equipment manufacturer generally provides a tapping for 
insertion of the temperature controller sensing element. The 
tapping should be located at a point where average system 
temperature will be measured. Never locate the sensing 
element close to a hot or cold water inlet or a steam coil, or 
where the well’s pressure rating will be exceeded.
Turn off power and, if the system is filled, drain to a point below 
the boiler tapping or wherever the sensing element is to be 
located. If no tapping is provided, prepare one, properly 
threaded, at the desired location.
If this is a remote bulb unit, the controller case can be mounted 
in a panel or, with the optional bracket, on any flat surface. 
Choose a location within reach of the sensing element. Allow 
for gradual bends and some slack in the capillary.
Mount the Immersion Well
1. Coat the well threads with a moderate amount of pipe 
dope, leaving two end threads bare. Teflon
®
 tape may 
also be used.
2. Screw the immersion well into the tapping and tighten 
securely.
3. Refill the system. Check for and correct any leaks.
Fig. 2. Use good Piping Practice when Installing 
Immersion Well.
To Install Direct Mount Controller
1. Slide the sensing bulb all the way into the well. The metal 
collar around the capillary should slip into the well spud.
2. Line up the case so the setting indicator is on top.
3. Tighten the setscrew in the well spud snugly against the 
metal collar.
Fig. 3. The Direct Mount Model is held in place by the 
Setscrew in the Well Spud.
To Mount Remote Bulb Controller
Insert Sensing Bulb in Well
1. Slide sensing bulb into well. Make sure bulb rests 
against the bottom of the well. Don’t bend the capillary 
where it connects to the bulb.
2. Hold bulb in place and tighten setscrew all the way 
down. It won’t fit tight against the capillary, but it will keep 
the bulb from sliding out.
Fig. 4. The Setscrew keeps the Remote Sensing Bulb in 
the Well.
USE MODERATE AMOUNT
OF PIPE COMPOUND
LEAVE 2 END THREADS BARE
M25415
CONTROLLER
SETSCREW
SPUD
WELL
BULB
CAPILLARY
METAL
COLLAR
M25416
SETSCREW
SPUD
CAPILLARY
CAPILLARY
SETSCREW
SPUD
BULB
WELL
M25417