AIR FOR COMBUSTION AND VENTILATION
Continued
Confined and Unconfined Space
The National Fuel Gas Code, ANSI Z223.1/
NFPA 54
 defines a confined space as a space 
whose volume is less than 50 cubic feet per 
1,000 Btu per hour (4.8 m
3
 per kw) of the ag-
gregate input rating of all appliances installed 
in that space and an unconfined space as a 
space whose volume is not less than 50 cubic 
feet per 1,000 Btu per hour (4.8 m
3
 per kw) 
of the aggregate input rating of all appliances 
installed in that space. Rooms communicating 
directly with the space in which the appliances 
are installed*, through openings not furnished 
with doors, are considered a part of the un-
confined space.
* Adjoining rooms are communicating only if 
there are doorless passageways or ventilation 
grills between them.
DETERMINING FRESH-AIR FLOW 
FOR HEATER LOCATION
Determining if You Have a Confined or 
Unconfined Space
Use this work sheet to determine if you have 
a confined or unconfined space.
Space: Includes the room in which you will 
install heater plus any adjoining rooms with 
doorless  passageways  or  ventilation  grills 
between the rooms.
1.  Determine the volume of the space (length 
x width x height).
 
Length x Width x Height =__________cu. ft. 
(volume of space)
 
Example: Space size 20 ft. (length) x 16 ft. 
(width) x 8 ft. (ceiling height) = 2560 cu. ft. 
(volume of space)
 
If  additional  ventilation  to  adjoining  room 
is supplied with grills or openings, add the 
volume of these rooms to the total volume 
of the space.
2.  Multiply the space volume by 20 to determine 
the maximum Btu/Hr the space can support.
 
  ________ (volume of space) x 20 = (Maxi-
mum Btu/Hr the space can support)
 
Example: 2560 cu. ft. (volume of space) x 20 
=  51,200  (maximum  Btu/Hr  the  space  can 
support)
3.  Add the Btu/Hr of all fuel burning appliances 
in the space.
 
Vent-free fireplace 
 __________ Btu/Hr
 
Gas water heater* 
 __________ Btu/Hr
 
Gas furnace 
 __________ Btu/Hr
 
Vented gas heater 
 __________ Btu/Hr
 
Gas fireplace logs 
 __________ Btu/Hr
 
Other gas appliances* + ________ Btu/Hr
 
Total 
= _________ Btu/Hr
 
* Do not include direct-vent gas appliances. 
Direct-vent  draws  combustion  air  from  the 
outdoors and vents to the outdoors.
 
Example: 
 
Gas water heater 
 _________ Btu/Hr
 
Vent-free fireplace 
+ ________ Btu/Hr
 
Total 
 _________ =  Btu/
Hr
4.  Compare the maximum Btu/Hr the space can 
support with the actual amount of Btu/Hr used.
 
  _____ Btu/Hr  (maximum  the  space  can 
support) 
 
 ______Btu/Hr (actual amount of Btu/Hr used)
 
Example:  51,200  Btu/Hr  (maximum  the 
space can support)
 
 
73,000 Btu/Hr (actual amount of 
Btu/Hr used)
The space in the above example is a confined 
space because the actual Btu/Hr used is more 
than  the  maximum  Btu/Hr  the  space  can  sup-
port. You must provide additional fresh air. Your 
options are as follows:
A.  Rework worksheet, adding the space of an 
adjoining room. If the extra space provides 
an unconfined space, remove door to adjoin-
ing  room  or  add  ventilation  grills  between 
rooms.  See  Ventilation  Air  From  Inside 
Building
, page 8.
B.  Vent  room  directly  to  the  outdoors.  See 
Ventilation Air From Outdoors, page 8.
C.  Install a lower Btu/Hr fireplace, if lower Btu/Hr 
size makes room unconfined.
If the actual Btu/Hr used is less than the maxi-
mum Btu/Hr the space can support, the space is 
an unconfined space. You will need no additional 
fresh air ventilation.
 WARNING: If the area in which 
the heater may be operated does 
not meet the required volume for 
indoor combustion air, combus-
tion and ventilation air shall be 
provided by one of the methods 
described  in  the  National  Fuel 
Gas Code, ANSI Z223.1/NFPA 54, 
the International Fuel Gas Code, 
or applicable local codes.
  40,000
  33,000
  73,000