Crestron clt-4hsw4 clx-4hsw4 ユーザーズマニュアル

ページ / 4
 
CLT- & CLX-4HSW4 
Functional Summary 
NOTE:  Modules and terminal blocks must be installed 
into the lowest available spaces and continue toward the 
top of the enclosure. 
The Crestron
 4-Feed, 4-High Switch Terminal Block and 
Module (CLT-4HSW4 and CLX-4HSW4, respectively), 
are considered a single entity and must be used together. 
They ship separately to permit termination of the field 
wiring to the CLT-4HSW4 prior to installation of the 
CLX-4HSW4, as described in this guide. They can be 
mounted in any Crestron Automation Enclosure (CAEN-
Series Enclosures). The terminal block is designed to 
terminate four circuit feeds (LINE and NEUTRAL) and 
distribute the controlled circuits (LOAD) to the fixtures. 
The module connects to the terminal block and performs 
switching (non-dim) control of four incandescent, low 
voltage, neon, cold cathode, fluorescent, or HID lighting 
loads, or motor loads. The maximum load is 16 amps (1/2 
HP) for each controlled circuit (64 amps total per 
module). The unit requires 120VAC 60 Hz input voltage. 
An oversize heat sink dissipates heat efficiently. There are 
LEDs on the module to indicate communication to a 
Cresnet
 network, input power to the module, and output 
power to the load. 
Terminal Block & Module Locations (Single-wide Enclosure) 
MODULE
TERMINAL
BLOCK
GROUNDING
TERMINAL
BLOCK
 
 
Industry Compliance 
This product is Listed to applicable UL Standards and 
requirements by Underwriters Laboratories Inc.  
Terminal Block & Module Locations (Double-wide Enclosure) 
     
(E103692)
 
GROUNDING TERMINAL BLOCKS
MODULE
TERMINAL BLOCK
(LEFT)
TERMINAL BLOCK
(RIGHT)
 
Installation 
Terminal block and module must be mounted into a 
Crestron Automation Enclosure by a licensed electrician, 
in accordance with all national and local codes.  
CAUTION:  This equipment is for indoor use only and 
needs to be air-cooled. Mount in a well-ventilated area. 
The ambient temperature must be 32
°F to 104°F (0°C to 
40
°C). The relative humidity must be 0% to 90% (non-
condensing).  
Terminal blocks are installed along the left side of single-
wide enclosures and along the outside edges (left and 
right sides) of double-wide enclosures. Modules are 
installed along the right side of single-wide enclosures 
and side-by-side in the center of double-wide enclosures. 
When installing modules and terminal blocks in a double-
wide enclosure, be sure to invert units on the right side so 
that they can be properly wired. Refer to the illustrations 
shown in the next column when considering the location 
of terminal blocks and modules within an enclosure.  
Crestron Electronics, Inc.
 
Installation Guide – DOC. 5986C
 
15 Volvo Drive   Rockleigh, NJ 07647
 
(2002068)
 
Tel: 888.CRESTRON
 
11.06
 
Fax: 201.767.7576
  
Specifications subject to 
 
www.crestron.com
 
change without notice.