DSC pc1616 ユーザーズマニュアル

ページ / 64
Section 4 – Programming Descriptions
19
Section [380] First Communicator Option Code
Section [381] Second Communicator Option Code
Section [382] Third Communicator Option Code
Option
Description
 [1]
ON: the system communicator is enabled.  OFF: the communicator is disabled.
 [2]
ON: the system transmits alarm restorals if the zone is restored and the bell has timed out.  OFF: the system transmits alarm restorals 
immediately when the zone is restored.
 [3]
ON: the panel uses rotary (pulse) dialing.  OFF: the panel uses touchtone (DTMF) dialing
 [4]
ON: the panel will switch from touchtone dialing to rotary dialing after the 4th failed attempt to communicate.
OFF: the panel will use rotary dialing for all dialing attempts.
 [5]
ON: the system uses the Third Phone Number to back up the First Phone Number.  OFF: the Third Phone Number is disabled.
 [6]
ON: the system alternates between the First Phone Number and Third Phone Number when attempting to report an event.  
OFF: the panel will dial the First Phone Number for the programmed number of attempts, then switch to the Third Phone Number.
 [7]
For future Use
 [8]
ON: the Delinquency feature follows zone activity.  OFF: the Delinquency feature follows arming.
Option
Description
 [1]
ON: the keypad beeps 8 times after successfully transmitting the Opening After Alarm reporting event. OFF: the keypad does not beep.
 [2]
ON: the bell output squawks 8 times after successfully transmitting the Opening After Alarm reporting event.  OFF: the bell output does 
not activate.
 [3]
ON: the system uses programmed reporting codes when transmitting using the SIA format.  
OFF: the system automatically generates all reporting codes transmitted.
 [4]
ON: the system beeps the keypad 8 times after successfully transmitting a Closing reporting event. OFF: the keypad does not beep.
 [5]
ON: the system requests a Listen in/Two-way session the next time it calls the 1st/3rd Phone Number when the PC59xx transmits a 
request.  OFF: the system ignores the request from the PC59xx.
This Option is used with PC59xx series modules.
 [6]
ON: the system requests a Listen in/Two-way session the next time it calls the 2nd Phone Number when the PC59xx transmits a request.  
OFF: the system will ignore the request from the PC59xx.
This Option is used with PC59xx series modules.
 [7]
ON: the system uses Contact ID format programmed reporting codes when transmitting reporting codes.  
OFF: the system automatically generates all reporting codes transmitted.
 [8]
For Future Use
Option
Description
 [1]
ON: the system will use the digit [5] as the first digit of the Partial Closing reporting code when transmitting Contact ID reporting codes.  
OFF: the system will use the digit [4] as the first digit of the Partial Closing reporting code when transmitting Contact ID reporting codes.
 [2]
ON: the system will transmit all alarms during Walk Test.  OFF: the system will not report alarm events during Walk Test.
 [3]
ON: the keypad will display the message ‘Communications Cancelled’ (programmable LCD) or ‘CC’ (fixed-message LCD) upon 
successful transmission of the Communication Cancelled reporting event.  OFF: the keypad will not display these messages.
 [4]
ON: the system dials the Call Waiting Cancel String on the first attempt to dial the central station.  OFF: the system does not dial the Call 
Waiting Cancel String.
 [5]
ON: enables support for the T-Link module.  OFF: disables T-Link.