WIRING DIAGRAMS
SILENCE
NORMAL
TEST
ON
OFF
SILENCE
NORMAL
TEST
SILENCE
NORMAL
TEST
SILENCE
NORMAL
TEST
SILENCE
NORMAL
TEST
120/240 VAC Single Phase
120/208 VAC Three Phase Wye
277/480 VAC Three Phase Wye
480 VAC Three Phase Delta
120/240 VAC Three Phase High Leg Delta
L1
L2
L3
N
G
L1
L2
L3
N
G
L1
L2
L3
N
G
L1
L2
N
G
L1
L2
L3
G
BLACK
BLACK
BLACK
WHITE
GREEN
BLACK
BLACK
BLACK
WHITE
GREEN
BLACK
BLACK
BLACK
GREEN
BLACK
RED
BLACK
WHITE
GREEN
BLACK
BLACK
WHITE
GREEN
Figure 1
Figure 5
Figure 3
Figure 4
SILENCE
NORMAL
TEST
L1
L2
L3
N
G
BLACK
BLACK
BLACK
WHITE
GREEN
Figure 2
NOTE: For convenience and working safety, these wiring
diagrams show installation on the load side of a breaker.
PG Series 4000, 4500 and 5000 systems may be installed
without an external breaker.  Refer to installation instruc-
tion number 4 on page 1.
M
ODELS
:
PG4001-240-2S
PG4501-240-2S
PG5001-240-2S
M
ODELS
:
PG4001-208-3Y
PG4501-208-3Y
PG5001-208-3Y
M
ODELS
:
PG4001-600-3Y
PG4501-600-3Y
PG5001-600-3Y
M
ODELS
:
PG4001-480-3Y
PG4501-480-3Y
PG5001-480-3Y
M
ODELS
:
PG4001-480-3D
PG4501-480-3D
PG5001-480-3D
M
ODELS
:
PG4001-240-3HLD
PG4501-240-3HLD
PG5001-240-3HLD
ALARM RELAY OUTPUT CONNECTIONS
1. Two Wire Closed Loop: Connect feed wire  to the Common (C)
wire and return wire to the Normally Opened (N/O) wire. During
normal operation, the contact will be closed between C and N/O.
The contact will open during an alarm condition.
2. Two Wire Opened Loop: Connect the feed wire to the Common
( C ) wire and return wire to the Normally Closed (N/C) wire.
During normal operation, the contact will be opened between C
and N/C.  The contact will close during an alarm condition.  
3. Three Wire Supervised Loop: Connect feed wire to the
Common (C) wire, one return wire to the Normally Opened (N/O)
wire and the second return wire to the Normally Closed (N/C)
wire.  During normal operation, the contact will be closed between
C and N/O and opened between C and N/C. An alarm condition
will reverse the condition. 
4. Consult the instructions for your specific monitoring system for
additional information.
2
Brown - c
Brown - c
Violet - n/c
Orange - n/o
Orange - n/o
Violet - n/c
Normal operating condition - relay energized
Alarm condition - relay not energized
SUGGESTED WIRE SIZES
SERIES
UNDER 3’
UNDER 6’
OVER 6’
PG4000
8 AWG
6 AWG
4 AWG
PG4500
6 AWG
4 AWG
2 AWG
PG5000
4 AWG
2 AWG
2 AWG
347/600 VAC Three Phase Wye
Figure 6
SILENCE
NORMAL
TEST
600 VAC Three Phase Delta
L1
L2
L3
G
BLACK
BLACK
BLACK
GREEN
Figure 7
M
ODELS
:
PG4001-600-3D
PG4501-600-3D
PG5001-600-3D