FMI pfs us vshrp16t ユーザーズマニュアル

ページ / 28
www.fmiproducts.com
125311-01A
6
DETERMINING FRESH-AIR FLOW 
FOR HEATER LOCATION
Determining if You Have a Confined or 
Unconfined Space
Use this work sheet to determine if you have 
a confined or unconfined space.
Space: Includes the room in which you will install 
heater plus any adjoining rooms with doorless 
passageways  or  ventilation  grills  between  the 
rooms.
1.  Determine the volume of the space (length 
x width x height).
 
Length x Width x Height =__________cu. ft. 
(volume of space)
 
Example: Space size 20 ft. (6.1m) (length) x 
16 ft. (4.88m) (width) x 8 ft. (2.44 m) (ceiling 
height) = 2,560 cu. ft. (72.49 m
2
)(volume of 
space)
 
If  additional  ventilation  to  adjoining  room 
is supplied with grills or openings, add the 
volume of these rooms to the total volume 
of the space. 
2.  Multiply the space volume by 20 to determine 
the maximum Btu/Hr the space can support.
 
  ________ (volume of space) x 20 = (Maxi-
mum Btu/Hr the space can support)
 
Example: 2,560 cu. ft. (72.49 m
2
) (volume of 
space) x 20 = 51,200 (maximum Btu/Hr the 
space can support)
3.  Add the Btu/Hr of all fuel burning appliances 
in the space.
 
Vent-free heater 
   _________ Btu/Hr
 
Gas water heater*     _________ Btu/Hr
 
Gas furnace 
   _________ Btu/Hr
 
Vented gas heater     _________ Btu/Hr
 
Gas heater logs 
   _________ Btu/Hr
 
Other gas appliances* +  _________ Btu/Hr
 
Total 
=  _________ Btu/Hr
 
* Do not include direct-vent gas appliances. 
Direct-vent draws combustion air from the 
outdoors and vents to the outdoors.
 
Example: 
 
Gas water heater 
   _________ Btu/Hr
 
Vent-free heater 
+  _________ Btu/Hr
 
Total 
=  _________ Btu/Hr
4.  Compare  the  maximum  Btu/Hr  the  space 
can support with the actual amount of Btu/
Hr used.
 
  _______ Btu/Hr (maximum can support) 
 
  _______ Btu/Hr (actual amount used)
 
Example:  51,200  Btu/Hr  (maximum  the 
space can support) 
 
 
60,000 Btu/Hr (actual amount of 
Btu/Hr used)
AIR FOR COMBUSTION AND VENTILATION
Continued
The space in the example is a confined space 
because the actual Btu/Hr used is more than the 
maximum  Btu/Hr  the  space  can  support. You 
must provide additional fresh air. Your options 
are as follows:
A.  Rework worksheet, adding the space of an 
adjoining room. If the extra space provides an 
unconfined space, remove door to adjoining 
room or add ventilation grills between rooms. 
See Ventilation Air From Inside Building.
B.  Vent  room  directly  to  the  outdoors.  See 
Ventilation Air From Outdoors, page 7.
C.  Install a lower Btu/Hr heater, if lower Btu/Hr 
size makes room unconfined. 
If the actual Btu/Hr used is less than the maxi-
mum Btu/Hr the space can support,
 the space is 
an unconfined space. You will need no additional 
fresh air ventilation.
 WARNING: If the area in which 
the heater may be operated does 
not meet the required volume for 
indoor combustion air, combus-
tion and ventilation air shall be 
provided by one of the methods 
described in the National Fuel 
Gas Code, ANSI Z223.1/NFPA 54, 
the International Fuel Gas Code, 
or applicable local codes.
vENTILATION AIR
Ventilation Air From Inside Building 
This fresh air would come from an adjoining 
unconfined  space.  When  ventilating  to  an 
adjoining unconfined space, you must provide 
two permanent openings: one within 12" (30.5 
cm) of the ceiling and one within 12" (30.5 cm) 
of  the  floor  on  the  wall  connecting  the  two 
spaces (see options 1 and 2, Figure 2, page 
7). You can also remove door into adjoining 
room (see option 3, Figure 2, page 7). Follow 
the National Fuel Gas Code, ANSI Z223.1/
NFPA 54, Air for Combustion and Ventilation 
for required size of ventilation grills or ducts.
40,000
60,000
20,000