Desa WMP10 ユーザーズマニュアル

ページ / 60
www.desatech.com
123995-01C
6
AIR FOR COMBUSTION AND VENTILATION
Continued
DETERMINING FRESH-AIR FLOW 
FOR FIREPLACE LOCATION
Determining if You Have a Confined or 
Unconfined Space
Use this work sheet to determine if you have 
a confined or unconfined space.
Space: Includes the room in which you will install 
fireplace  plus  any  adjoining  rooms  with  door-
less passageways or ventilation grills between 
the rooms.
1.  Determine the volume of the space (length 
x width x height).
 
Length x Width x Height =__________cu. ft. 
(volume of space)
 
Example: Space size 20 ft. (length) x 16 ft. 
(width) x 8 ft. (ceiling height) = 2,560 cu. ft. 
(volume of space)
 
If  additional  ventilation  to  adjoining  room 
is supplied with grills or openings, add the 
volume of these rooms to the total volume 
of the space. 
2.  Multiply the space volume by 20 to determine 
the maximum Btu/Hr the space can support.
 
  ________ (volume of space) x 20 = (Maxi-
mum Btu/Hr the space can support)
 
Example:  2,560  cu.  ft.  (volume  of  space)  x 
20 = 51,200 (maximum Btu/Hr the space can 
support)
3.  Add the Btu/Hr of all fuel burning appliances 
in the space.
 
Vent-free heater 
 __________Btu/Hr
 
Gas water heater* 
 __________Btu/Hr
 
Gas furnace 
 __________Btu/Hr
 
Vented gas heater 
 __________Btu/Hr
 
Gas fireplace logs 
 __________Btu/Hr
 
Other gas appliances* + _________Btu/Hr
 
Total 
= _________Btu/Hr
 
* Do not include direct-vent gas appliances. 
Direct-vent  draws  combustion  air  from  the 
outdoors and vents to the outdoors.
 
Example:
 
Gas water heater 
 __________Btu/Hr
 
Vent-free heater 
+ _________Btu/Hr
 
Total 
= _________Btu/Hr
4.  Compare  the  maximum  Btu/Hr  the  space 
can support with the actual amount of Btu/Hr 
used.
 
  _______ Btu/Hr (maximum can support) 
 
  _______ Btu/Hr (actual amount used)
 
Example:  51,200  Btu/Hr  (maximum  the 
space can support)
 
 
60,000 Btu/Hr (actual amount of 
Btu/Hr used)
The space in the example is a confined space 
because the actual Btu/Hr used is more than the 
maximum  Btu/Hr  the  space  can  support.  You 
must  provide  additional  fresh  air. Your  options 
are as follows:
A.  Rework worksheet, adding the space of an 
adjoining room. If the extra space provides 
an unconfined space, remove door to adjoin-
ing  room  or  add  ventilation  grills  between 
rooms.  See  Ventilation  Air  From  Inside 
Building.
B.  Vent  room  directly  to  the  outdoors.  See 
Ventilation Air From Outdoors, page 7.
C.  Install a lower Btu/Hr heater, if lower Btu/Hr 
size makes room unconfined.
If the actual Btu/Hr used is less than the maxi-
mum Btu/Hr the space can support, the space 
is an unconfined space. You will need no ad-
ditional fresh air ventilation.
 WARNING: If the area in which 
the heater may be operated does 
not meet the required volume for 
indoor combustion air, combus-
tion and ventilation air shall be 
provided by one of the methods 
described  in  the  National  Fuel 
Gas Code, ANSI Z223.1/NFPA 54, 
the International Fuel Gas Code, 
or applicable local codes.
VENTILATION AIR
Ventilation Air From Inside Building
This fresh air would come from an adjoining 
unconfined  space.  When  ventilating  to  an 
adjoining unconfined space, you must provide 
two  permanent  openings:  one  within  12"  of 
the ceiling and one within 12" of the floor on 
the wall connecting the two spaces (see op-
tions 1 and 2, Figure 2, page 7). You can also 
remove door into adjoining room (see option 
3, Figure 2, page 7). Follow the National Fuel 
Gas  Code,  ANSI  Z223.1/NFPA  54,  Air  for 
Combustion and Ventilation
 for required size 
of ventilation grills or ducts.
50,000
10,000
60,000