Intermatic ug40 modular ユーザーズマニュアル

ページ / 4
WIRING DIAGRAMS
120/240 VAC Single Phase
120/208 VAC Three Phase Wye
277/480 VAC Three Phase Wye
480 VAC Three Phase Delta
120/240 VAC Three Phase High Leg Delta
240 VAC Three Phase Delta
240 VAC Ground Phase Delta
UG40A2401S
UG40A2403D
UG40A2083Y
UG40A2403G
UG40A4803D
UG40A4803Y
L1
L2
L3
N
G
L1
L2
L3
N
G
L1
L2
L3
N
G
L1
L2
N
G
L1
L2
L3
G
L1
L2
L3
G
BLACK
BLACK
BLACK
WHITE
GREEN
BLACK
BLACK
BLACK
WHITE
GREEN
BLACK
BLACK
BLACK
GREEN
BLACK
BLACK
BLACK
GREEN
BLACK
RED
BLACK
WHITE
GREEN
BLACK
BLACK
WHITE
GREEN
ALARM RELAY OUTPUT CONNECTIONS
1. Two Wire Closed Loop: Connect feed wire  to the Common ( C ) terminal and return wire to the Normally Opened 
(N/O) terminal. During normal operation, the contact will be closed between C and N/O.  The contact will open dur
ing an alarm condition. (Refer to Figure 7)
2. Two Wire Opened Loop: Connect the feed wire to the Common ( C ) terminal and return wire to the Normally 
Closed (N/C) terminal. During normal operation, the contact will be opened between C and N/C.  The contact will 
close during an alarm condition. (Refer to Figure 8) 
3. Three Wire Supervised Loop: Connect feed wire  to the Common ( C ) terminal, one return wire to the Normally 
Opened (N/O) terminal and the second return wire to the Normally Closed (N/C)  terminal.  During normal opera-
tion, the contact will be closed between C and N/O and opened between C and N/C. An alarm condition will 
reverse the condition. (Refer to Figure 9) 
4. Consult the instructions for your specific monitoring system for additional information.
Figure 1
Figure 6
Figure 3
Figure 5
Figure 2
Figure 4
N/O
C
N/C
N/O
C
N/C
N/O
C
N/C
Figure 7
Figure 8
Figure 9
2
NOTE:
For convenience sake, these wireing diagrams show installation on the load side of a breaker.  UG40 systems may
be installed without an external breaker.  Refer to installation instruction number 4 on page 1.