Honeywell R7184B ユーザーズマニュアル

ページ / 8
R7184A,B,P,U INTERRUPTED ELECTRONIC OIL PRIMARY
7
69-1233—2
4. Shield cad cell from external light.
Indicator light turns 
off.
Eliminate external light source or permanently shield 
cad cell.
Indicator light stays 
on.
Replace cad cell with new cad cell and recheck.
If indicator light does not turn off, remove cad cell 
leadwires from R7184 and recheck.
If indicator light turns off, replace cad cell bracket 
assembly. Refer to TRADELINE® Catalog for 
bracket part numbers.
If indicator light does not turn off, replace 
controller.
5. On warm air systems, jumper 
thermostat (T to T) terminals on R7184.  
(On hydronic systems jumper Limit 
terminal and L1 of R7184.)
IMPORTANT:
First remove one thermostat 
lead.
Burner starts.
Trouble in thermostat or limit circuit. Check 
thermostat or limit wiring connections.
Burner does not start. •
Disconnect line voltage power and open line 
switch.
Check all wiring connections.
Tighten any loose connections and recheck.
If burner does not start, replace R7184.
Condition: Burner starts, then locks out on safety with indicator light flashing at 1 Hz rate (1/2 second on, 1/2 
second off)
.
 1. Check that limit switches are closed 
and contacts are clean.
 2. Check for line voltage power at the 
oil primary control. Voltage should be 
120 Vac.
 3. Check indicator light with burner off, 
no call for heat (no flame).
Indicator light is on.
Cad cell or controller is defective, sees external light 
or connections are shorted. Go to step 4.
Indicator light is off.
Go to step 5.
 4. Shield cad cell from external light.
Indicator light turns 
off.
Eliminate external light source or permanently shield 
cad cell.
Indicator light stays 
on.
 Replace cad cell with new cad cell and 
recheck.
 If indicator light does not turn off, remove cad 
cell leadwires from R7184 and recheck.
 If indicator light turns off, replace cad cell 
bracket assembly. Refer to TRADELINE
®
 
catalog for bracket part numbers.
 If indicator light does not turn off, replace 
controller.
 5. On warm air systems, jumper 
thermostat (T to T) terminals on R7184. 
(On hydronic systems, jumper Limit 
terminal and L1 of R7184.)
IMPORTANT: 
First remove one thermostat lead.
Burner starts.
Trouble is in thermostat or limit circuit. Check 
thermostat or limit wiring connections.
Burner does not start. •
Disconnect line voltage power and open line 
switch.
 Check all wiring connections.
 Tighten any loose connections and recheck.
 If burner does not start, replace R7184.
Condition: Burner starts then locks out on safety with indicator light flashing at 1 Hz rate (1/2 second on, 1/2 
second off)
6. Reset oil primary control by pushing 
in and releasing red reset button.
Indicator light stops 
flashing.
Go to step 7.
Indicator light 
continues to flash at 
1 Hz rate
a
.
Verify that control is not in restricted mode (see 
footnote a). If not in restricted mode, replace R7184.
Table 5. Troubleshooting Information (Continued).
Procedure
Status
Corrective Actions