Crestron clt-1delv4 clx-1delv4 ユーザーズマニュアル

ページ / 4
 
CLT- & CLX-1DELV4 
Functional Summary 
The Crestron
 1-Feed, 4-Dimmer Electronic Low Voltage 
Terminal Block and Module (CLT-1DELV4 and  
CLX-1DELV4, respectively), are considered a single 
entity and must be used together. They ship separately to 
permit termination of the field wiring to the  
CLT-1DELV4 prior to installation of the CLX-1DELV4, 
as described in this guide. They can be mounted in any 
Crestron Automation Enclosure (CAEN-Series 
Enclosures). The terminal block is designed to terminate 
the circuit feed (HOT and NEUTRAL) and distribute the 
controlled circuit (LOAD) to the fixture(s). The module 
connects to the terminal block and performs dimming 
control of four electronic low-voltage or incandescent 
loads. The maximum load is 10 amps for any controlled 
circuit, limited to 16 amps total per module. The unit 
requires 120VAC 60 Hz, 1 phase input voltage. An 
oversize heat sink dissipates heat efficiently. There are 
LEDs on the module to indicate communication to a 
Cresnet
 network, input power to the module, and output 
power to the load. 
NOTE:  When connecting to an Arc Fault Breaker, 
the load should not exceed 1000 watts.  
Industry Compliance 
This product is Listed to applicable UL Standards and 
requirements by Underwriters Laboratories Inc. 
     
(E103692)
 
Installation 
The terminal block and module must be mounted into a 
Crestron Automation Enclosure by a licensed electrician, 
in accordance with all national and local codes.  
CAUTION:  This equipment is for indoor use only 
and needs to be air-cooled. Mount in a well-
ventilated area. The ambient temperature must be 
32
°F to 104°F (0°C to 40°C). The relative humidity 
must be 0% to 90% (non-condensing).  
Terminal blocks are installed along the left side of single-
wide enclosures and along the outside edges (left and 
right sides) of double-wide enclosures. Modules are 
installed along the right side of single-wide enclosures 
and side-by-side in the center of double-wide enclosures. 
When installing modules and terminal blocks in a double-
wide enclosure, be sure to invert units on the right side so 
that they can be properly wired. Refer to the illustrations 
shown in the next column when considering the location 
of terminal blocks and modules within an enclosure.  
NOTE:  Modules and terminal blocks must be 
installed into the lowest available spaces and 
continue toward the top of the enclosure. 
Terminal Block & Module Locations (Single-wide Enclosure) 
CRESTRON
N OUT 4
N OUT 3
N OUT 2
N OUT 1
1 FEED
120VAC 60 Hz
16A MAX
9A MAX/CKT
CLX-1DELV4
GROUNDING
TERMINAL
BLOCK
DIM 4
DIM 3
DIM 1
DIM 2
4 DIM
LINE
TERMINAL
BLOCK
N IN
MODULE
 
Terminal Block & Module Locations (Double-wide Enclosure) 
Crestron Electronics, Inc.
 
Installation Guide – DOC. 5989A
 
15 Volvo Drive   Rockleigh, NJ 07647
 
(2002071)
 
Tel: 888.CRESTRON
 
08.05
 
Fax: 201.767.7576
  
Specifications subject to 
 
www.crestron.com
 
change without notice.
 
TERMINAL BLOCK
(RIGHT)
CRESTRON
N OUT 4
GROUNDING TERMINAL BLOCKS
TERMINAL BLOCK
(LEFT)
N OUT 3
N OUT 2
N IN
N OUT 1
DIM 4
DIM 3
DIM 1
DIM 2
LINE
1 FEED
120VAC 60 Hz
16A MAX
9A MAX/CKT
4 DIM
CLX-1DELV4
MODULE
N OUT 4
N OUT 3
N OUT 2
N OUT 1
N IN
DIM 4
DIM 3
DIM 2
DIM 1
LINE
CRESTRON
CLX-1DELV4
120VAC 60 Hz
16A MAX
9A MAX/CKT
1 FEED
4 DIM