hubbell-lighting lightning rod ground conn ユーザーズマニュアル
LIGHTNING ROD OPTION GROUND
CONNECTIONS AT BOTTOM OF POLE
THIS LIGHTNING ROD SYSTEM INSTALLATION
MUST MEET NFPA 780 CODE REQUIREMENTS
STEEL POLE
SECURE POLE CONNECTORS
(SHIPPED W/CROSSARM)
TO POLE HANDHOLE FRAME
10'-6" COPPER CABLES
(SHIPPED W/CROSSARM)
CONCRETE POLE
SECURE CABLES TO POLE
CONNECTORS & GRD RODS
GROUND LINE
POLE HANDHOLE FRAME
SECURE POLE CONNECTORS
TO EMBEDDED INSERT
COPPER CABLE FROM POLE
10' (MIN)
(20' IN SANDY SOILS)
8" RAD
(MIN)
90
°
(MIN)
GROUND ROD CONNECTOR
(SHIPPED W/CROSSARM)
5/8” DIA GROUND ROD
(FURNISHED BY CONTRACTOR)
GROUND ROD NOTES:
• TWO REQUIRED PER POLE
• PLACEMENT SHOULD BE 180
• TWO REQUIRED PER POLE
• PLACEMENT SHOULD BE 180
°
APART
• RODS TO BE PLACED 2’ (MIN) AWAY
FROM POLE BASE