INSTALLATION INSTRUCTIONS FOR
SLS TWO CIRCUIT REMOTE BALLAST SYSTEM
Catalog Logic:  R  E  M  D - X X X X  H  X - XX - XX
Fixture Watts:
1000
1500
1650
Fixture Voltage:
(2) 208v
(3) 240v
(4) 277v
(5) 480v
Circuit No. 1 & 2 Ballast Qty:
51 42 33 41 32 31 22 21 11
Optional Features:
(SH) Solution Harness Ready
(TB) **Thermal Magnetic Breaker
**Standard for 240v and below
(WP) Wood or other Solid Pole
(T) Wire Three Phase
A complete system includes the ballast enclosure, lighting
fixtures, wiring harness, crossarms and poles.
Warning!
• Dangerous voltages exist within this product.
• This enclosure includes two electrical supply circuits. To
reduce fire and shock hazards disconnect power to both
circuits before servicing.
• To reduce the risk of injury, operate and maintain to meet
all applicable codes.
• Installation is to be performed by a qualified electrician
only.
• Provide proper ground for all system components.
• Read and follow all instructions and labels before and dur-
ing installation.
• Failure to properly install this product will void
manufacturer’s warranty.
• Handle and secure so ballast enclosure cannot fall.
• Use protective equipment to avoid injury during installa-
tion of this heavy product.
• Do not route wiring through top of enclosure.
    This ballast enclosure should be installed at a minimum
height of 10 feet (3 meters) above grade.
Enclosure Installation (Figures 1, 2, & 3)
Important: Installation requires the use of a pole equipped
with mounting couplings and wireway. (Figure 1)
1. Remove peel strip from gasket supplied in hardware bag.
2. Apply gasket to the back of enclosure around the 2-1/2"
x 4-1/2" (63.5mm x 114.3mm) hole. (Figure 3)
3. Install bolt (2) and lockwasher (3) in the top coupling.
(Figure 2) Leave 1" (25.4mm) of thread exposed.
268-1220-9901
3/8"
TYP.
3/8"
3"
41"
5"
4-7/8"
COUPLING W/ 3/4-10
INTERNAL THREADS
FOR 3/4" BOLT
FIGURE 1
FIGURE 2