Panasonic CZCSWGC2 操作ガイド
8
9
:Switches between “swing” and “F1” to “F3” every time it is clicked.
:Switches between “Auto”, “High”, “Mid”, and “Low” every time it is
clicked.
:Changes the room temperature setting.
*The setting temperature range can be changed on the screen
displayed by selecting “Maintenance” - “Register I/D unit high/low-
limit temperature”.
limit temperature”.
:Transmits set content to the I/D unit.
4-1-2-3.
Start/stop control method (digital point)
Click the
button while a digital point is selected to display the ON/OFF
screen.
Click the
Click the
button to close the ON/OFF screen.
:Click this button to transmit the start signal and close the screen.
:Click this button to transmit the stop signal and close the screen.
4-1-2-4.
Start/stop control method (analog point)
Use this method to change the output
value of the analog output.
Display the popup menu for the analog
point as shown in “4-1-3-3. How to
display popup menu”. Click “Output
value settings” in the menu to display
the “Output value settings” screen.
Change the output value.
value of the analog output.
Display the popup menu for the analog
point as shown in “4-1-3-3. How to
display popup menu”. Click “Output
value settings” in the menu to display
the “Output value settings” screen.
Change the output value.
Then click the
button to set the analog output value and close the
screen.
Click the
Click the
button to close the screen without changing the value.