Panasonic CZCSWKC2 操作ガイド
4-21. R/C prohibition settings
[Procedure]
On the menu bar, select “Maintenance” – “R/C prohibition settings”.
On the menu bar, select “Maintenance” – “R/C prohibition settings”.
(Password level 1)
Set the prohibition items for each central control mode, which the central system (P-AIMS) uses
to prohibit the remote control units of indoor units from exercising control functions.
to prohibit the remote control units of indoor units from exercising control functions.
The image above shows the initial values.
:Indicates prohibition. (This mark can be changed)
:Indicates prohibition. (This mark cannot be changed)
:Indicates permission. (This mark can be changed)
:Indicates permission. (This mark cannot be changed)
:Initializes central control mode.
:Registers changes to settings.
:Restores changes to their previous settings.
:Closes the window.
Central control mode display
Prohibit 1: The remote control unit cannot be used for switching On/Off. (The mode can be
changed)
Prohibit 2: The remote control unit cannot be used for switching On/Off, temperature setting
and operation mode switching. (The mode can be changed)
Prohibit 3: The remote control unit cannot be used for temperature setting and operation
mode switching. (The mode can be changed)
Prohibit 4: The remote control unit cannot be used for operation mode switching. (The mode
can be changed)
Prohibit 5: The remote control unit cannot be used for switching On/Off. (The mode cannot be
changed)
Prohibit 6: The remote control unit cannot be used for switching On/Off, temperature setting
and operation mode switching. (The mode cannot be changed)
Prohibit 7: The remote control unit cannot be used for temperature setting and operation
mode switching. (The mode cannot be changed)
* Prohibit 1–4 are for the CZ-CFUNC2.