4-21.  R/C prohibition settings
[Procedure]
  On the menu bar, select “Maintenance” – “R/C prohibition settings”. 
(Password level 1)
Set the prohibition items for each central control mode, which the central system (P-AIMS) uses 
to prohibit the remote control units of indoor units from exercising control functions.
The image above shows the initial values.
 
  :Indicates prohibition. (This mark can be changed)
 
  :Indicates prohibition. (This mark cannot be changed)
 
  :Indicates permission. (This mark can be changed)
 
  :Indicates permission. (This mark cannot be changed)
    :Initializes central control mode.
    :Registers changes to settings.
    :Restores changes to their previous settings.
    :Closes the window.
Central control mode display
 
Prohibit 1:  The remote control unit cannot be used for switching On/Off. (The mode can be 
changed)
 
Prohibit 2:  The remote control unit cannot be used for switching On/Off, temperature setting 
and operation mode switching. (The mode can be changed)
 
Prohibit 3:  The remote control unit cannot be used for temperature setting and operation 
mode switching. (The mode can be changed)
 
Prohibit 4:  The remote control unit cannot be used for operation mode switching. (The mode 
can be changed)
 
Prohibit 5:  The remote control unit cannot be used for switching On/Off. (The mode cannot be 
changed)
 
Prohibit 6:  The remote control unit cannot be used for switching On/Off, temperature setting 
and operation mode switching. (The mode cannot be changed)
 
Prohibit 7:  The remote control unit cannot be used for temperature setting and operation 
mode switching. (The mode cannot be changed)
*  Prohibit 1–4 are for the CZ-CFUNC2.