Hirschmann RPS90/48V HV Power Supply 仕様ガイド

ページ / 2
 
Hirschmann Automation and Control GmbH  
www.beldensolutions.com
 
05-08-2014
Page 1 of 2
 
Product information
RPS90/48V HV
Industrial Ethernet:System Accessories:Power supply:RPS90/48V HV
Name
RPS90/48V HV
 
48 V DC rail power supply unit
Delivery informations
Availability
available
Product description
Description
48 V DC rail power supply unit
Type
RPS90/48V HV
Order No.
943 979-001
More Interfaces
Voltage input
1 terminal block, 3-pin
Voltage output
1 terminal block, 4-pin
Power requirements
Operating voltage
60 / 120 / 250 V DC (48-320 V) und 110 / 230 V AC
Input data
Input voltage
100-240 V AC; 50-60 Hz oder 85 bis 264 V AC; 47-63 Hz (DC 100-375 V)
Current consumption
Current consumption
60 V DC (1.7 A), 250 V DC (0.4 A), 110 V AC (1.0 A), 230 V AC (0.5 A)
Activation current
N/A
Output data
Output voltage
48 - 54 V DC (typ. 48 V); externally adjustable
Output current
Output current
1.9 A static at 48 V nominal
Service
Diagnostics
LED (green)
Redundancy
Redundancy functions
redundant power supply
Ambient conditions
Operating temperature
-40 ºC bis +50 ºC
Storage/transport temperature
-40 ºC bis +85 ºC
Relative humidity (non-condensing)
max. 95 % without condensation
MTBF
N/A
Mechanical construction
Dimensions (W x H x D)
60 mm x 137 mm x 115 mm
Mounting
DIN Rail
Weight
740 g
Protection class
IP 30
EMC interference immunity
EN 50082-1
EN 61000-6-1
EN 50082-2
EN 61000-6-2 (including EN 55024), EN 61850-3, IEEE 1613, EN 50121-4, 50121-3-2, GL (pending)
EMC emitted immunity
EN 50081-1
61000-6-3
EN 50081-2
61000-6-4, EN 55011, EN 55022 Klasse A, GL (pedning), Netzrückwirkungen gemäß EN 61000-3-2
Approvals
Safety of industrial control equipment
cUL 508 (pending)
Safety of information technology equipment
cUL 60950-1 (pending)
Shipbuilding
Germanischer Lloyd, ABS