Puls CS5.241 Power Supply 仕様ガイド

ページ / 20
 
 
 
CS5.241, CS5.241-C1, CS5.241-S1 
 
  CSeries 
24V, 5A, S
INGLE 
P
HASE 
I
NPUT
 
 
 
Dec. 2006 / Rev. 1.3  DS-CS5.241-EN 
All parameters are specified at 24V, 5A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. 
www.pulspower.com   Phone +49 89 9278 0    Germany 
4/20 
 
6. I
NPUT 
I
NRUSH 
C
URRENT 
S
URGE
 
 
An active inrush limitation circuitry limits the input inrush current after turn-on of the input voltage. 
The charging current into EMI suppression capacitors is disregarded in the first milliseconds after switch-on. 
 
 
AC 100V 
AC 120V 
AC 230V 
 
 Inrush 
current 
max. 
10A
peak
 10A
peak
 10A
peak
 
-25°C to +70°C 
   
typ. 
3A
peak
 3A
peak
 3A
peak
 
-25°C to +70°C 
 Inrush 
energy 
typ. 
1A
2
s 1A
2
s 1A
2
-25°C to +70°C 
 
 
Fig. 6-1   Input inrush current, typical behavior 
 
 
 
 
Input Current
Input Voltage
Output Voltage
A
 
 
A: 
 
Start-up delay = Inrush delay 
Input:    
230Vac 
Output:  
24V, 5A 
Ambient: 25°C 
Upper curve: 
Input current 10A / DIV 
Medium curve:  Input voltage 500V / DIV 
Lower curve: 
Output voltage 20V / DIV 
Time scale:  
100ms / DIV 
 
 
 
7. H
OLD
-
UP 
T
IME
 
 
   
AC 100V 
AC 120V 
AC 230V 
 
  Hold-up Time 
typ. 
109ms 
165ms 
161ms 
2,5A, 24V, see 
Fig. 7-1
 
 
 
typ. 
50ms 80ms 78ms 
5A, 
24V, 
see 
Fig. 7-1
 
 
 
typ. 
37ms 62ms 63ms 
6A, 
24V, 
see 
Fig. 7-1
 
 
 
Fig. 7-1   Hold-up time vs. input voltage 
 
Fig. 7-2   Shut-down behavior, definitions 
 
0
25
50
150ms
85
120
100
180
230Vac
Hold-up Time
100
75
125
Input Voltage
a) 24V 2,5A typ.
b) 24V 2,5A min.
c) 24V 5A typ.
d) 24V 5A min.
e) 24V 6A min.
a
a
b
c
c
d
d
e
e
b
 
 
- 5%
Hold-up Time
Zero Transition
Output
Voltage
Intput
Voltage
 
Note:  At no load, the hold-up time can be up to several seconds. The green DC-ok lamp is on during this time.