Cisco CATALYST 6509E 9 SLOT 15U CHASSIS NO POWER SUPPLY NO FAN TRAY 仕様ガイド

ページ / 336
A-45
Catalyst 6500 Series Switches Installation Guide
OL-5781-04
Appendix A      Power Supply Specifications
  6000 W AC-Input Power Supply
System power dissipation
7034 W 
Branch circuit requirement (AC-input)
Each power supply input should have its own 
dedicated, fused-branch circuit:
For North America—20 A
For International—Circuits should be sized 
according to local and national codes
All Catalyst 6500 series AC-input power supplies 
require single-phase source AC.
All AC power supply inputs are fully isolated.
Source AC can be out of phase between 
multiple power supplies in the same chassis, 
which means that PS1 can be operating from 
phase A and PS2 can be operating from 
phase B.
Source AC can be out of phase between AC 
inputs on power supplies that are equipped 
with multiple AC inputs, which means that 
power cord 1 can be plugged into phase A and 
power cord 2 can be plugged into phase B.
Power supply output
2900 W operation (one 220 VAC source or two 
110 VAC sources)
25 A @ +3.3 V
12 A @ +12 V
63.6 A @ +42 V
6000 W operation (two 220 VAC sources)
25 A @ +3.3 V
12 A @ +12 V
137.4 A @ +42 V
Output holdup time
20 ms minimum
Heat Dissipation
23,812 BTU/hour (approx.)
Table A-19 6000 W AC-Input Power Supply Specifications (continued)
Specification
Description