Installation Guide
page 26 
18-HD72D1-1 
5.3.7 Advanced Settings — Lockouts
MENU ITEM
OPTIONS [DEFAULT]
DESCRIPTION
Auxiliary Heat Lockout
[Disable], Enable
Enable auxiliary heat lockout (10° minimum separation when enabling 
auxiliary heat lockout and compressor heat lockout)
Auxiliary Heat Lockout
32°F - 70°F Degrees [45°]
Select an outdoor temperature to prevent auxiliary heat above the selected 
outdoor temperature
Compressor Lockout
[Disable], Enable
Enable compressor heat lockout (10° minimum separation when enabling 
auxiliary heat lockout and compressor heat lockout)
Compressor Lockout
5°F - 35°F Degrees [30]
Select an outdoor temperature to prevent compressor heating below the 
selected outdoor temperature
Defrost Heater Balance Point (W1)
[Disable], Enable
Enable defrost heater balance point for W1, W2 and W3 (only applicable 
when indoor heat is electric or hydronic)
Defrost Heater Balance Point (W1)
40°F - [55°F]
Select an outdoor temperature to disallow 1st, 2nd and 3rd stage of indoor 
heat during defrost above this temperature
Defrost Heater Balance Point (W2)
[Disable], Enable
Enable defrost heater balance point for W1 and W2 (only applicable when 
indoor heat is electric or hydronic)
Defrost Heater Balance Point (W2)
10°F - 50°F [55°F]
Select an outdoor temperature to disallow 2nd and 3rd stage of indoor heat 
during defrost above this temperature
Defrost Heater Balance Point (W3)
[Disable], Enable
Enable defrost heater balance point for W3 only (only applicable when indoor 
heat is electric or hydronic)
Defrost Heater Balance Point (W3)
[5°F] - 35°F 
Select an outdoor temperature to disallow 3rd stage of indoor heat during 
defrost above this temperature
Compressor Cooling 1st Stage Lockout [Disable], Enable
Enable compressor cooling 1st stage lockout
Compressor Cooling 1st Stage Lockout 80°F - [120°F] 
Select an outdoor temperature to force the system to 2nd stage compressor 
cooling
Compressor Heating 1st Stage Lockout [Disable], Enable
Enable compressor heating 1st stage lockout
Compressor Heating 1st Stage Lockout 0°F - [50°F] 
Select an outdoor temperature to force the system to 2nd stage compressor 
heating
Furnace Heating 1st Stage Lockout
[Disable], Enable
Enable furnace heating 1st stage lockout
Furnace Heating 1st Stage Lockout
0°F - [50°F] 
Select an outdoor temperature to force the system to 2nd stage furnace 
heating