5.3.7 Advanced Settings — Lockouts
MENU ITEM
OPTIONS [DEFAULT]
DESCRIPTION
Auxiliary Heat Lockout
[Disable], Enable
Enable auxiliary heat lockout (10° minimum separation when enabling
auxiliary heat lockout and compressor heat lockout)
auxiliary heat lockout and compressor heat lockout)
Auxiliary Heat Lockout
32°F - 70°F Degrees [45°]
Select an outdoor temperature to prevent auxiliary heat above the selected
outdoor temperature
outdoor temperature
Compressor Lockout
[Disable], Enable
Enable compressor heat lockout (10° minimum separation when enabling
auxiliary heat lockout and compressor heat lockout)
auxiliary heat lockout and compressor heat lockout)
Compressor Lockout
5°F - 35°F Degrees [30]
Select an outdoor temperature to prevent compressor heating below the
selected outdoor temperature
selected outdoor temperature
Defrost Heater Balance Point (W1)
[Disable], Enable
Enable defrost heater balance point for W1, W2 and W3 (only applicable
when indoor heat is electric or hydronic)
when indoor heat is electric or hydronic)
Defrost Heater Balance Point (W1)
40°F - [55°F]
Select an outdoor temperature to disallow 1st, 2nd and 3rd stage of indoor
heat during defrost above this temperature
heat during defrost above this temperature
Defrost Heater Balance Point (W2)
[Disable], Enable
Enable defrost heater balance point for W1 and W2 (only applicable when
indoor heat is electric or hydronic)
indoor heat is electric or hydronic)
Defrost Heater Balance Point (W2)
10°F - 50°F [55°F]
Select an outdoor temperature to disallow 2nd and 3rd stage of indoor heat
during defrost above this temperature
during defrost above this temperature
Defrost Heater Balance Point (W3)
[Disable], Enable
Enable defrost heater balance point for W3 only (only applicable when indoor
heat is electric or hydronic)
heat is electric or hydronic)
Defrost Heater Balance Point (W3)
[5°F] - 35°F
Select an outdoor temperature to disallow 3rd stage of indoor heat during
defrost above this temperature
defrost above this temperature
Compressor Cooling 1st Stage Lockout [Disable], Enable
Enable compressor cooling 1st stage lockout
Compressor Cooling 1st Stage Lockout 80°F - [120°F]
Select an outdoor temperature to force the system to 2nd stage compressor
cooling
cooling
Compressor Heating 1st Stage Lockout [Disable], Enable
Enable compressor heating 1st stage lockout
Compressor Heating 1st Stage Lockout 0°F - [50°F]
Select an outdoor temperature to force the system to 2nd stage compressor
heating
heating
Furnace Heating 1st Stage Lockout
[Disable], Enable
Enable furnace heating 1st stage lockout
Furnace Heating 1st Stage Lockout
0°F - [50°F]
Select an outdoor temperature to force the system to 2nd stage furnace
heating
heating