DIXELL S.r.l. 01XRCHC ユーザーズマニュアル

ページ / 7
 
XRB60CHC EN r1.1 2018.11.01.docx 
                           XRB60CHC 
2/7 
 
7. 
When Aid=1, the first day will be used to analyze the temperature behavior and to build the 
model to apply to the second day. The model will be updated every day in order to better match 
the working conditions. 
8. 
When Aid=7, the first 7 days will be used to analyze the temperature behavior and to build the 
model to apply to the next 7 days. The model will be updated every 7 days in order to better 
match the working conditions. 
9. 
When Aid=7, the first 7 days after power on will use a sub analysis base on 1-day model. 
10. 
nCE is used to define the minimum duration of an energy saving interval of time 
11. 
nCC is used to move the SET-POINT value from normal mode value to the energy saving 
mode value by steps (1 step = 1°C or 1°F, starting from the SET value and increasing it every 
30 min till reaching the SET_ES value) 
12. 
Pdt is used to anticipate the end of the energy saving mode in order to decrease the 
temperature of the bottles before starting the normal mode interval 
13. 
PPU select the probe used for automatic energy saving algorithm 
14. 
tun is used to change the sensibility of the automatic energy saving algorithm. tun=H (high) is 
used for cabinet with regulation probe installed near the evaporator air outlet flow. tun=L (low) 
is used for cabinet with regulation probe installed far away from the evaporator air outlet flow. 
EXTRA COOLING FUNCTION 
 
 
The extra cooling function (named Pull Down) is active when the room temperature measured from the probe 
1 goes over the SET+oHt+HY value. In this case, a special set-point value, lower than the normal SET value, 
will  be  enabled.  As  soon  as  the  room  temperature  reaches  the  SET+CCS  value,  the  compressor  will  be 
stopped and the normal regulation will restart. N.B.: pull down function is disabled when CCS=0 or CCt=0
The CCt parameter sets the maximum activation time for any pull down. When CCt expires, the pull down will 
be immediately stopped and the standard SET-POINT will be restored. NOTE: in case of energy saving mode 
active, the used values will be: SET_ES=SET+HES, oHE and CCS. 
EVAPORATOR FANS 
 
 
With FnC parameter it can be selected the fans functioning: 
•  FnC=C-n  fans will switch ON and OFF with the compressor and not run during defrost; when 
compressor  is  OFF,  fans  will  enter  a  duty-cycle  working  mode  (see  FoF,  Fon,  FF1  and  Fo1 
parameters). 
•  FnC=o-n  fans will run even if the compressor is off, and not run during defrost; 
•  FnC=C-Y    fans  will  switch  ON  and  OFF  with  the  compressor  and  run  during  defrost;  when 
compressor  is  OFF  all  fans  will  enter  a  duty-cycle  working  mode  (see  FoF,  Fon,  FF1  and  Fo1 
parameters). 
•  FnC=o-Y  fans will run continuously also during defrost. 
 
After defrost, there is a timed fan delay allowing for drip time, set by means of the Fnd parameter. 
An  additional  parameter  FSt  provides  the  setting  of  temperature,  detected  by  the  evaporator  probe, 
above which the fans are always OFF. By using this parameter it is possible to assure air circulation 
only if air temperature is lower than FSt value. 
6.1 
EVAPORATOR FAN AND DIGITAL INPUT 
When the digital input is configured as door switch (i1F=dor), fans and compressor status will depend on the 
odC parameter value:  
• 
odC=no 
 normal regulation 
• 
odC=FAn 
 evaporator fan OFF 
• 
odC=CPr 
 compressor OFF 
• 
odC=F-C 
 compressor and evaporator fan OFF 
 
When rrd=Y the regulation will restart after a door open alarm. 
DEFROST 
7.1 
DEFROST MODE 
Any defrost operation can be controlled in the following way: 
EdF=rtC: by using an internal real time clock (only for models equipped with RTC). 
EdF=in: timed defrost, in this case a new defrost will start as soon as the idF timer elapses. 
EdF=Aut: automatic management, in this case the controller will start a new defrost any time a 
change from normal to energy saving mode will occur (valid if ErA=Aut). 
7.2 
TIMED OR PROBE CONTROLLED MODE 
Two  defrost  modes  are  available:  timed  or  controlled  by  the  evaporator’s  probe.  A  couple  of 
parameters is used to control the interval between defrost cycles (idF) and its maximum length (MdF). 
During  the  defrost  cycle  is  possible  to  select  some  different  display  indications  by  using  the  dFd 
parameter. These modes are available with any kind of defrost type: 
tdF=EL: electric heater defrost 
tdF=in: hot gas defrost. 
7.3 
AUTOMATIC DURATION DETECTION 
When  a  defrost  operation  is  performed  by  compressor  stop  (means  by  stopping  the  compressor  and  by 
activating the internal ventilators), it will be possible to use an automatic defrost mode by setting od2=ALt. In 
this case the device will use the evaporator probe (which MUST to be present and properly mounted on the 
evaporator surface)  to detect the end of the actual defrost  phase. In any case, a  maximum  period  of time 
(MdF) and an upper evaporator temperature value will be used to stop the current defrost phase.  If ErA=Aut
the automatic defrost mode will activate a defrost at the beginning of any energy saving mode period.  In this 
case the idF delay is used as safety function. It forces the controller to activate a defrost operation when idF 
runs. NOTE: during the defrost phase the loads (compressor and evaporator fans) will be controlled from the 
defrost algorithm. 
INTERNAL COUNTERS 
The next table shows the implemented load and function of total counters. 
 
n1H 
Number of relay output 1 activation (thousands of) 
n1L 
Number of relay output 1 activation (hundreds of) 
n2H 
Number of relay output 2 activation (thousands of) 
n2L 
Number of relay output 2 activation (hundreds of) 
n3H 
Number of relay output 3 activation (thousands of) 
n3L 
Number of relay output 3 activation (hundreds of) 
n4H 
Number of relay output 4 activation (thousands of) 
n4L 
Number of relay output 4 activation (hundreds of) 
n5H 
Number of digital input 1 activation (thousands of) 
n5L 
Number of digital input 1 activation (hundreds of) 
n6H 
Number of digital input 2 activation (thousands of) 
n6L 
Number of digital input 2 activation (hundreds of) 
oCH 
Compressor working hours (thousands of) 
oCL 
Compressor working hours (hundreds of) 
 
In this way it is possible to monitor the application and discovering bad functioning that could lead to damages. 
They are updated in EEPROM every hour. It is not possible to reset them. 
NOTE: the compressor activation counters take into account also defrost in case of inversion (hot gas) mode. 
8.1  AUX RELAY CONFIGURATION (PAR. oAX) 
An  auxiliary  relay  can  be  set  by  the  oAx  parameters,  according  to  the  kind  of  application.  In  the 
following paragraph the possible settings. 
8.1.1  Light relay 
With oAx=LiG the AUX relay operates as light output. 
8.1.2  Auxiliary relay 
a. 
Relay  activation  by  digital  input  1  or  digital  input  2  (oAx=AUS,  i1F  or  i2F=AUS):  with 
oAx=AUS and i1F, i2F=AUS the AUX relay is switched on and off by digital inputs. 
b. 
Auxiliary thermostat: anti condensing heater with the possibility of switching it on and off also 
by using the frontal keyboard. 
Parameters involved:  
ACH: kind of regulation for the auxiliary relay: Ht = heating; CL = cooling. 
SAA: set point for auxiliary relay. 
SHy: differential for auxiliary relay. 
ArP: probe for auxiliary relay. 
Sdd: auxiliary output off during defrost. 
Ao1: output active when in energy saving mode 
AF1: output not active when in energy saving mode 
 
The differential threshold value is set by the SHY parameter. 
 
NOTE:  
if oAx=AUS and ArP=nP (no probe for auxiliary output) the AUX relay can be activated  
by digital input if i1F=AUS or i2F=AUS 
by auxiliary button (if set as AUS
by serial command (Modbus protocol) 
by fixed interval of time if Ao1>0 and AF1>0 (if Ao1=0 or AF1=0 the auxiliary output is 
disabled)  
8.1.3  On/off relay (oAx = onF) 
When  oAx=onF, the  AUX  relay  is  activated  when  the  controller  is  turned  on  and de-activated  when 
the controller is turned off. 
8.1.4  Neutral zone regulation 
With oAx=db the AUX relay can control a heater element to perform a neutral zone action. 
• 
oA1 cut in = SET-HY 
• 
oA1 cut out = SET