4.0 Mounting 
 
When mounting the Nano Prox Proximity Reader please 
respect the following guidelines. 
 
•  Avoid wiring the Nano Prox cables in the same conduit 
with AC power cables, lock power, or signal wiring. 
•  Maintain all reader wiring a minimum of 12" (30cm) 
away  from  other  wiring  such  as  AC  power,  computer 
data wiring, telephone wiring and wiring to electric lock 
devices. 
•  Avoid installing within 3.5 feet (1.1m) of computer 
monitors or CRTs. The minimum distance will vary 
depending on the type of monitor or CRT. 
•  Avoid installing in proximity to sources of broad 
spectrum EMI noise such as motors, pumps, 
generators, DC to AC converters, uninterruptible power 
supplies, AC switching relays, light dimmers, computer 
monitors and CRTs. 
•  Avoid installing in proximity to potential sources of high 
power RF signal transmitters such as cellular 
telephones and two way radios.  
 
5.0 Wiring Connection 
 
Two wiring methods can be used. Dual LED operation 
allows the signalling of both LED's independently using the 
LED control lines. Single LED allows a single LED line to 
control both LED colours. 
 
 
 
Figure 1 - Dual LED Connection 
 
 
 
Figure 2 - Single LED Connection 
 
Using the recommended cables listed in the technical 
specifications in section 7, splice these cables together 
with the pigtail of the reader and seal the splice. Route the 
cable from the reader to the host controller. Connect the 
cables as shown in Figure 1 for Dual LED Operation or 
Figure 2 for Single LED Operation. 
 
Do not connect the shield wires together at the 
reader cable splice. With the shield wire 
already terminated at the reader terminate the 
shield at the controller. For more information 
refer to Figure 1 and Figure 2. 
 
6.0 Button Input Wiring Connection 
 
Button input wiring configuration is shown in Figure 2. For 
programming options refer to the Protégé System Manual. 
 
 
 
Figure 3 - Button Input Wiring 
 
Connect a normally open button or switch as shown in 
figure 2 and complete the programming within the Protégé 
Integrated System for the functionality required.  
 
External Button Input Mode and single LED 
operation must be enabled when using this 
wiring configuration. 
 
7.0 Specifications 
 
Power Supply 
 
Voltage 
 
12VDC (9.5 - 14.0VDC) 
Current 
 
120mA (Peak, Reading) 
 
Read Range 
 
 
 Card 
  Up 
to 
10cm 
(4") 
 Tag 
  Up 
to 
6cm 
(2.5") 
 
Interface 
 
Wiegand 
 
Multiple Format 26, 34, 37 Bit 
 
 
 
 
Data 0 and Data 1 
Distance 
 
150 Meters (500 feet)   
 
Frequency 
 Field 
  125KHz 
Pulse 
Width 
Modulated 
 
Cable 
Type    
 
Multi Conductor  22Awg Alpha 5196, 5198 
    18Awg 
Alpha 
5386, 
5388 
    18Awg 
Beldon 
9553 
 
Temperature 
 Operating 
 -35˚- +65˚ Celsius 
 
 
 
-31˚ - 149˚ Fahrenheit 
 
*Specifications are subject to change without notice, 
please visit www.integratedcontroltechnology.com for the 
updated information. Read range is specified using an ICT 
card format and the card is presented parallel to the 
reader using installation procedures detailed in this 
manual without any electrical interference present.