System Inlet Temperature
System Inlet Temperature
System Inlet Temperature
System Inlet Temperature Operating
10° to 35°C (50° to 95°F) at sea level with an
altitude derating of 1.0°C per every 305 m
(1.8°F per every 1000 ft) above sea level to a
maximum of 3050 m (10,000 ft), no direct
sustained sunlight. Maximum rate of change is
10°C/hr (18°F/hr). The upper limit may be
limited by the type and number of options
installed.
System performance may be reduced if operating
with a fan fault or above 30°C (86°F).
Non-operating
-30° to 60°C (-22° to 140°F). Maximum rate of
change is 20°C/hr (36°F/hr).
Relative Humidity
Relative Humidity
Relative Humidity
Relative Humidity
(non-condensing)
Operating
10 to 90% relative humidity (Rh), 28°C (82.4°F)
maximum wet bulb temperature, non-
condensing.
Non-operating
10 to 95% relative humidity (Rh), 38.7°C
(101.7°F) maximum wet bulb temperature, non-
condensing.
Altitude
Altitude
Altitude
Altitude
Operating
3048 m (10,000 ft). This value may be limited by
the type and number of options installed.
Maximum allowable altitude change rate is 457
m/min (1500 ft/min).
Non-operating
9144 m (30,000 ft). Maximum allowable
altitude change rate is 457 m/min (1500 ft/min).
Acoustic Noise
Acoustic Noise
Acoustic Noise
Acoustic Noise
Listed are the declared A-Weighted sound power levels (LWAd) and declared
average bystander position A-Weighted sound pressure levels (LpAm) when
the product is operating in a 23°C ambient environment. Noise emissions
were measured in accordance with ISO 7779 (ECMA 74) and declared in
accordance with ISO 9296 (ECMA 109).
Idle
Idle
Idle
Idle
 
L WAd
4.6 B for 1P Non-Redundant; 4.9 B for 2P
Redundant
L pAm
28 dB for 1P Non-Redundant; 31 dB for 2P
Redundant
Operating
Operating
Operating
Operating
 
L WAd
4.7 B for 1P Non-Redundant; 5.0 B for 2P
Redundant
L pAm
29 dB for 1P Non-Redundant; 32 dB for 2P
Redundant
NOTE: 
NOTE: 
NOTE: 
NOTE: The Listed sound levels apply to standard shipping configurations.
Additional options may result in increased sound levels.
Emissions Classification
Emissions Classification
Emissions Classification
Emissions Classification
(EMC)
FCC Rating
Class B
Normative Standards
CISPR 22; EN55022; EN55024; FCC CFR 47,
Pt 15; ICES-003; CNS13438; GB9254;
K22;K24; EN 61000-3-2; EN 61000-3-3; EN
60950-1; IEC 60950-1
QuickSpecs
HP ProLiant DL370 Generation 6 (G6)
HP ProLiant DL370 Generation 6 (G6)
HP ProLiant DL370 Generation 6 (G6)
HP ProLiant DL370 Generation 6 (G6)
HP ProLiant ML370 Generation 6 (G6)
HP ProLiant ML370 Generation 6 (G6)
HP ProLiant ML370 Generation 6 (G6)
HP ProLiant ML370 Generation 6 (G6)
Technical Specifications
DA - 13242   North America — Version 47 — November 18, 2011
Page 59