KROHNE FMCW24G74T ユーザーズマニュアル

ページ / 136
6
 OPERATION 
72 
OPTIWAVE 7400-24 C
www.krohne.com
12/2015 - 4004901901 - MA OPTIWAVE7400-24 R01 fr
You can change the reference point from which distance is measured. Use this menu 
item:
• Reference Offset (2.3.7)
6.4.6  Level measurement
The device displays level measurements when the output function is set to "Level".
 Menu items related to level measurement are:
• Output Function (2.4.1)
• Tank Height (2.3.1)
• Blocking Distance (2.3.2)
You can change the reference point from which level is measured. Use this menu item:
• Tank Bottom Offset (2.3.8)
INFORMATION!
If you move the reference point above the flange, add this value when you give a distance for the 
4 and 20 mA current output settings. If you move the reference point below the flange, subtract 
this value when you give a distance for the 4 and 20 mA current output settings.
CAUTION!
If the distance for 4 mA is set in the blocking distance, the device will not be able to use the full 
current output range.
Figure 6-4: Distance measurement
1  Tank Height (2.3.1)
2  Reference Offset (2.3.7)
3  Blocking Distance (2.3.2)
4  4 mA  Setting  (2.4.3)
5  20 mA Setting (2.4.4)
6  Maximum effective measuring range
7  Non-measurement zone