Lutron Electronics Company Inc 0062 ユーザーズマニュアル

ページ / 1
Designer-Style RF Maestro
®
  
Dimmers: RRD-6D, RRD-10D, RRD-10ND
Switch: RRD-8ANS 
Typical Power Consumption*: 0.2 W
Remote Dimmer: RD-RD
Remote Switch: RD-RS 
Typical Power Consumption*: 0 W
120 V
  50 / 60 Hz
Installation Instructions
Please Read Before Installing
Multigang Installations
In multigang installations, several controls 
are grouped horizontally in one multigang 
wallbox.
When combining controls in a wallbox, 
derating is required; however, no derating 
is required for Remote Dimmers / Switches.
Derating Chart 
Control
Load 
Type
End of 
Gang
Middle of 
Gang
-6D
Incand.
500 W
400 W
MLV
400 W /  
500 VA
300 W /  
400 VA
-10D, 
-10ND
Incand.
800 W
650 W
MLV
600 W /  
800 VA
500 W /  
650 VA
-8ANS
Lighting
6.5 A
5 A
Motor
1/4 HP 
5.8 A
1/6 HP 
4.4 A
 
Note: -8ANS controls have fins that need 
to be removed for multigang installations.  
-6D, -10D, -10ND, -RD and -RS controls 
do not have fins that need to be removed 
for multigang installations.
Short Circuit Check: Check the 
installation for short circuits before 
installing control(s). With power OFF, install 
standard mechanical switch(es) between 
Hot and load. Restore power. If lights do 
not work or a breaker trips, check wiring. 
Correct wiring and check again. Install 
control(s) only when short is no longer 
present. Warranty is void if control is 
turned ON with a shorted circuit.
1.  Turn power OFF at fusebox or circuit 
breaker.
2.  Prepare wires. When making wire con-
nections, follow the recommended strip 
lengths and combinations for the sup-
plied wire connector.  
Note: Wire connector provided is suit-
able
 
for copper wire only.
Multi-Location Installation
2
-6D, -10D with RD-RD
Wiring Diagram 3
Single Location Installation with Neutral
-10ND, -8ANS
120 V
  
50 / 60 Hz
Brass
Silver
Black
Blue 
Tighten
1
Green
Ground
Hot/Live
Neutral
Load
Wiring Diagram 2
Single Location Installation
-6D, -10D
Wiring Diagram 1
Multi-Location Installation with Neutral
2, 3 
-10ND with RD-RD, and -8ANS with RD-RS
Dimmer / Switch 
3  Neutral wire Dimmers / Switches  must be connected on the Load side of a multi-location 
installation.
 Up to 9 Remote Dimmers / Switches may be connected to a Dimmer / Switch. Total blue 
terminal wire length may be up to 250 ft (76 m).
 When using controls in single location installations, tighten the blue terminal without 
any wires attached. DO NOT connect the blue terminal to any other wiring or to 
ground.
Status LEDs (Dimmer Only)
Indicate light level; glows softly as 
night light when load is off
Tapswitch
Tap on/off
Dimming Rocker
Press to Brighten
Press to Dim 
FASS
TM
Front
Accessible
Service
Switch
Dimmer Operation
Switch Operation
Lamp Replacement  
 
WARNING - Shock Hazard - For any procedure other than routine lamp 
replacement, power must be disconnected at the main electrical panel. Working 
with power ON could result in serious injury or even death. 
 
 
For your safety during routine lamp replacement, remove power from the fixture(s) 
by pulling the FASS switch out on both the Dimmer / Switch and all Remote 
Dimmers / Switches.
Troubleshooting Guide
Lutron Elec tron ics Co., Inc. 
7200 Suter Road
Coopersburg, PA 18036-1299
Made and print ed in the U.S.A.  7 / 09   P/N 044-157 Rev. A
Mounting Diagram
Control 
Mounting 
Screws
Wallbox
Control
Included:
Wire Connector (1)
Mounting Screws (2)
Adapter 
Mounting 
Screws
Wallplate adapter and 
wallplate purchased 
separately.
Dimmer
Status LED (Switch Only)
Indicates light status; glows softly 
as night light when load is off
Tapswitch
Tap on/off
FASS
Front
Accessible
Service
Switch
Brass
Black
Blue 
Tighten
1
Green
Ground
Hot/Live
Neutral
Lighting 
Load
Dimmer
Brass
Black
Blue
Green
Ground
Lighting 
Load
Dimmer
Brass
Black
Blue
Green
Ground
Remote Dimmer
120 V
  
50 / 60 Hz
Brass
Black
Blue
Green
Ground
Hot/Live
Neutral
Remote Dimmer
Brass
Silver
Black
Blue
Green
Ground
Load
Brass
Black
Blue
Green
Ground
Remote Dimmer/Switch
120 V
  
50 / 60 Hz
Brass
Black
Blue
Green
Ground
Hot/Live
Neutral
Remote Dimmer/Switch
Push-In Terminals: Insert 
wires fully. To release wire, 
insert small, flat screwdriver 
into slot below push-in 
terminal. Push screwdriver in 
while pulling wire out. Push-in 
terminals are for use with  
14 AWG (1.5 mm
2
)
 solid copper 
wire only. DO NOT use 
stranded or twisted wire. 
 
OR
Screw Terminals: Wrap 
wire around screw terminal. 
Tighten securely to 5 in-lbs 
(0.55 N•m). Screw terminals 
are for use with 12 AWG  
(2.5 mm
2
) or 14 AWG  
(1.5 mm
2
solid copper wire 
only. DO NOT use stranded or 
twisted wire.
Trim or strip wallbox wires to the length 
indicated by the strip gauge on the back of the 
control.
   Wire Connector: 
•  Strip insulation 3/8 in (10 mm) for 
14 AWG (1.5 mm
2
) or 12 AWG 
(2.5 mm
2
) wire
•  Strip insulation 7/16 in  
(11 mm) for 18 AWG (0.75 mm
2
wire
•  Use to join one or two 14 AWG   
(1.5 mm
2
) or 12 AWG
 
 (2.5 mm
2
wires with one 18 AWG  
(0.75 mm
2
) ground wire.
Twist wire  
connector 
tight.
Removing Fins on -8ANS
Each control 
has inside 
fins removed
Control at middle 
of Gang has all fins 
removed
Do Not remove outside fins on 
Controls at the end of gang
Control Location for Ganging
Installation
WARNING - To avoid the risk of 
electric shock
 locate and remove 
fuse or lock circuit breaker in the 
OFF position before proceeding. Wiring 
with power ON could result in serious 
injury or death.
Dimmer / Switch
Wiring Diagram 4
Switch
120 V
  
50 / 60 Hz
3.  Wire controls as follows: 
For single location installation:
 See 
Wiring Diagrams 1 and 2
For multi-location installation:
 See 
Wiring Diagrams 3 and 4.
4.  Push all wires back into the wallbox and 
loosely fasten the control to the wallbox 
using the control mounting screws pro-
vided. Do not pinch the wires.
5.  Attach the Lutron Claro or Satin Colors 
wallplate adapter and wallplate. 
  a.  Install wallplate adapter onto front of 
control(s).
  b.  Tighten control mounting screws until 
wallplate adapter is flush to wall (do 
not over-tighten).
  c.  Snap wallplate onto wallplate adapter, 
and verify that control is aligned prop-
erly.
  d.  If controls are misaligned, loosen 
mounting screws appropriately. 
6.  Restore power. Verify correct local 
operation (see 
Dimmer  Operation and 
Switch Operation).
Symptom
Probable Cause and Action
Lights don’t switch 
ON / OFF when 
Tapswitch on 
Dimmer / Switch/  
Remote is pressed
Power not present
   •  Circuit breaker OFF or tripped. Perform Short Circuit Check.
   •  FASS is in the OFF position. Move FASS to the ON position 
by fully pushing it in. Check both the Dimmer  / Switch and all 
of the Remote Dimmers / Switches.
Wiring
   •  Wires shorted. Make sure the blue terminal is not grounded 
or shorted to any other wires.
   •   Wiring error. Check wiring to be sure it agrees with 
installation instructions and wiring diagrams.
   •  Installed in a neutral-based location. Check that neutral-
based products are connected on the load side of a multi-
location installation (see Wiring Diagram 4).
Lamps burned out or not installed
   •   Replace or install lamps.
Dioded lamps
   •   If dioded lamps are being used, replace with non-dioded 
lamps.
Lights turn ON 
when Tapswitch is 
pressed, then turn 
OFF
Wiring
   •   Wiring error. Check wiring to be sure it agrees with 
installation instructions and wiring diagrams.
Tapswitch stuck
   •  Tapswitch stuck at another location. Check to see that 
tapswitches are not sticking for all control locations in the 
circuit.
Light turns ON and 
OFF continuously
Load is less than minimum load requirement
   •  Make sure the connected load meets the appropriate 
minimum load requirement for that control. See Load 
Specifications.
Lights don’t switch 
ON/OFF from a 
Keypad
Improper programming
   •  Program according to the system Setup Guide.
Out of RF range
   •  Reposition to be within 30 feet (9 m) of an RF Signal 
Repeater.
Wiring
   •  Wires shorted. Make sure the blue terminal is not grounded 
or shorted to any other wires.
   •   Wiring error. Check wiring to be sure it agrees with 
installation instructions and wiring diagrams.
Wallplate is warm
Solid-state control dissipation
   •  Solid-state dimmers and switches internally dissipate about 
2% of the total connected load. It is normal for dimmers and 
switches to feel warm to the touch during operation.
Use these instructions to install the 
model numbers listed above. For system 
setup instructions and tools visit  
www.lutron.com/radiora2
Load Specifications:
Control
Load 
Type
Min. 
Load
Max. 
Load
-6D
1
Incand.
50 W
600 W
MLV
2
50 W / VA
450 W /  
600 VA
-10D
1
Incand.
50 W
1000 W
MLV
2
50 W / VA
800 W /  
1000 VA
-10ND
1
Incand.
10 W
1000 W
MLV
2
10 W / VA
800 W /  
1000 VA
-8ANS
3
Lighting
10 W / VA
8 A
Motor
0.08 A
1/4 HP  
5.8 A
-RD
See Dimmer
8.3 A
-RS
See Switch
8.3 A
1  
Dimmer Load Type: -6D, -10D and -10ND are
    designed for use with permanently installed 
incandescent, magnetic low-voltage, or tung-
sten halogen only. Do not install dimmers to 
control receptacles or motor-operated appli-
ances. 
2  Low-Voltage Applications: Use -6D, 
-10D and -10ND with magnetic (core and coil) 
low-voltage transformers only. Not for use with 
electronic (solid-state) low-voltage transformers. 
3  Switch Load Type: -8ANS is designed for 
use with permanently installed incandescent, 
magnetic low-voltage, electronic low-voltage, 
or fluorescent loads and with motor loads up to 
1/4 HP (5.8 A).
Important Notes
WARNING - To avoid the risk 
of entrapment, serious injury, or 
death, these controls must not be 
used to control equipment which is not 
visible from every control location or which 
could create hazardous situations such 
as entrapment if operated accidentally. 
Examples of such equipment which must 
not be operated by these controls include 
(but are not limited to) motorized gates, 
garage doors, industrial doors, microwave 
ovens, heating pads, etc. It is the installer’s 
responsibility to ensure that the equip-
ment being controlled is visible from every 
control location and that only suitable 
equipment is connected to these controls. 
Failure to do so could result in serious 
injury or death.
Codes: Install in accordance with all local 
and national electrical codes.
Grounding: When no “grounding means” 
exist within the wallbox, then the NEC
®
 
2008, Article 404.9 allows a dimmer with-
out a grounding connection to be installed 
as a replacement, as long as a plastic, 
noncombustible wallplate is used. For 
this type of installation, cap or remove the 
green ground wire on the dimmer and use 
an appropriate wallplate such as Lutron’s 
Claro
®
 or Satin Colors
®
 wallplates. 
Neutral Wire: -10ND and -8ANS require 
a neutral wire connection in the wallbox 
where the Dimmer/Switch  is to be installed. 
If a neutral wire connection is not available 
in the wallbox, contact a licensed electri-
cian for installation. 
Environment: Ambient operating tempera-
ture: 32 °F to 104 °F (0 °C to 40 °C),  
0% to 90% humidity, non-condensing. 
Indoor use only.
Spacing: If mounting one control above 
another, leave at least 4 ½ in (114 mm) ver-
tical space between them.
Wallplates: Lutron
®
 Claro and Satin Colors 
wallplates are recommended for best color 
match and aesthetic appearance. Do not 
paint controls or wallplates.
Cleaning: To clean, wipe with a clean 
damp cloth. 
DO NOT use any chemical 
cleaning solutions.
Wallboxes: Lutron recommends using 
3 ½
 in (89 mm) deep wallboxes for eas-
ier installation. Several controls may be 
installed in one multigang wallbox — see 
Derating Chart.
Remote Dimmers / Switches: Use only 
Lutron Maestro Remote Dimmers (-RD) 
with -6D, -10D, and -10ND controls. Use 
only Lutron Maestro Remote Switches 
(-RS) with -8ANS controls. Up to 9 -RD or 
-RS controls may be used with Maestro 
Dimmers or Switches. Mechanical 3- or 
4-way switches will not work 
RF Device Placement: RF Dimmers and 
Switches must be located within 30 feet 
(9 m) of an RF Signal Repeater. Remote 
Dimmers and Switches are not required to 
be within a specific range of a repeater.
For systems with an RF signal repeater, RF 
Dimmers or Switches cannot be controlled 
by the system until they are programmed 
in a system according to the system Setup 
Guide.
English
Remote 
Dimmer
Remote 
Switch
These products may be covered under one or more of the following U.S. patents: 4,992,709; 5,248,919; 5,399,940; 5,637,930; 5,798,581; 5,838,226; 5,848,054; 5,905,442; 5,982,103; 6,169,377; 6,687,487; 6,803,728; 6,969,959; 7,071,634; 7,166,970; 7,190,125; 7,362,285; 
7,365,282; 7,382,100; 7,408,525; 7,548,216 and corresponding foreign patents. U.S. and foreign patents pending. NEC is a registered trademark of the National Fire Protection Association, Quincy, Massachusetts. Lutron, Claro, Satin Colors, Maestro, RadioRA and the 
sunburst logo are registered trademarks and RadioRA 2 and FASS are trademarks of Lutron Electronics Co., Inc.   
©2009 Lutron Electronics Co., Inc.
Wallplate 
Adapter
Wallplate
Returning Devices to Factory Settings
Note: Returning a control to its Factory Settings will remove the control from the system 
and erase all programming.
Step 1 :  Triple tap the tapswitch on the control. DO NOT release after the third tap.
Step 2 :  Keep the tapswitch pressed on the third tap (for approximately 3 seconds) until 
the status LEDs start to scroll up and down quickly.
Step 3 :  Release the tapswitch and immediately triple tap the tapswitch again. The status 
LEDs will scroll up and down slowly.
The control has now been returned to Factory Settings.
Warranty: For warranty information, please see the enclosed Warranty, or visit  
www.lutron.com/resiinfo.
Technical Assistance: 
U.S.A. / Canada: 1.800.523.9466 
Mexico: +1.888.235.2910 
Other Countries: +1.610.282.3800  
24 hours a day, 7 days a week.
* Typical Power Consumption test conditions: 
  Dimmer: load is off, nightlight mode enabled.
 Switch: load is off, nightlight mode enabled.
 Remote Dimmer / Switch: load is off.