TDC-1344-000 100T-CP Cathodic Protection Telemetry Module Installation Guide 
4  
 
Proprietary and Confidential 
 
 
 
 
This chapter provides the instructions to mount the 100T-CP on the test station post (riser pipe).   
 
Mounting Screw Specifications 
Application 
Itron Part 
Number 
 
Description 
To mount adapter plates on the 
pipe mounting bracket 
SCR-0215-002 
 
8-16 x 1/2-inch length, type 8 slotted pan-head/Phillips tapping 
screw, corrosion-resistant steel 
To mount 100T-CP modules 
on  the adapter plate 
SCR-0215-001 
 
8-16 x 1-inch type 8, slotted pan-head/Phillips tapping screw,  
corrosion-resistant steel 
To mount the 100T-CP 
modules on a wall or flat 
vertical surface 
SCR-0009-001 
 
10-16 x 1/2-inch type AB thread for sheet metal, Phillips  
pan-head tapping screw, corrosion-resistant steel 
 
Mounting Installation Considerations 
Mount the 100T-CP in a vertical position on the test station pipe with the telemetry module label directional 
arrow pointed upward.  
 
Caution  Upright vertical positioning is very important because: 
  100T-CP cathodic protection telemetry modules are designed with the antenna in a 
vertical direction so the antenna is parallel to the reading device (which has a vertical 
antenna). Matching antenna polarity can greatly affect RF performance and enable 
easy module reading. 
  100T-CP cathodic protection telemetry modules are designed so the tilt tamper is 
vertical. It is important to maintain vertical positioning in the field to enable tilt tamper 
stability. 
 
 
Warning  Do not mount the 100T-CP in an orientation other than vertical (module label arrow 
pointed upward). Violating the mounting orientation requirements will void the product 
warranty.    
Test for induced AC voltage on pipeline (using an accepted test procedure) prior to installing 
the 100T-CP module.  
 
 
 
C
H A P T E R  
2  
Mounting the 100T-CP Module on the Test Station Post