Ratings Compatibility
5
P3 (3G/GSM and Ethernet in redundant configuration, Panel Section [851][005] Toggle Option [5] ON). 
The Communicator can also be used as an Active communication system with the Security Levels A1-A4 (each channel 3G/GPRS or Ethernet indepen-
dent or together in a back-up/redundant configuration). For Active Line Security systems AES128 bit encryption shall be enabled (at the monitoring station
receiver) and the supervision heartbeat rate shall be set as 90 seconds (Panel Section [851][004] = 005A/90). The supervision window at the Signal
Receiver Center (SRC)'s receiver shall be programmed as maximum of 
180 (00B4/180) seconds.
For UL Residential Fire and Burglary applications the 3G2060R andTL2603GR can be used as the primary communication channel via either 3G/GSM or
Ethernet, or as a back-up in conjunction with the DACT 
(30 day test transmission is required on each channel). 
For UL Commercial Burglary applications the TL2603GR can be used as Dual Signalling Line communication system (3G/GPRS and Ethernet channels
used in redundant configuration), Standard Line Security and as Encrypted Line Security. 
The supervision heartbeat shall be enabled (Panel Section [851][005] Toggle Option [1] (Ethernet) and/or Toggle Option [2] (3G/GSM) shall be ON), Tog-
gle Option [3] (Supervision Type) shall be ON and the supervision heartbeat rate shall be selected as 135 (0087/135) seconds. Option [004] = 0087. The
supervision window at the supervising station shall be maximum 200 (00C8/200) seconds. For Encrypted Line Security systems the encryption AES128 bit
shall be enabled at the monitoring station receiver.
For UL Commercial Burglary installations, the 3G2060R is listed as a primary (sole) communication means (heartbeat must be enabled) or for supplemen-
tary (back-up) use in conjunction with a Plain Old Telephone Service (POTS) line dialer. When the heartbeat transmission over the Ethernet or 3G/GPRS
network is enabled, using the TL2603GR with a compatible control unit listed for standard/encrypted line security, it can provide line security for the alarm
system over the primary line. 
The TL2603GR is also suitable to be used with a compatible control unit listed for dual line security transmission when used in conjunction with a DACT or
a Public Switched Data Network (PSDN) transmitter, where the PSDN provides the line security and is the primary line. In this mode, alarm signals are
required to be sent simultaneously over both communication methods.
Ratings Compatibility
NOTE: Enter [*][8][Installer Code][900] at keypad to view the Panel Version number.
Products or components of products, which perform communications functions only shall comply with the requirements applicable to communications equip-
ment as specified in UL60950 or CAN CSA C22.2. No. 60950-1, Information Technology Equipment - Safety - Part 1: General Requirements. Where network
interfaces are internal to the control unit or receiver, compliance to CAN CSA C22.2. No. 60950-1 is adequate. Such components include, but are not limited
to: hubs; routers; NIDs; third-party communications service providers; DSL modems; and Cable modems.
C24 Interactive
NOTE: This application has not been investigated by UL/ULC and is not be used on UL/ULC certified installations.
The Communicator provides C24 Interactive monitoring and control via an RS-422 interface to an external C24-HUB. The default Keybus link speed is 115.2 
KB and this option is programmable by the installer.  All life-style events are transmitted by the RS-422 link to the C24-HUB and then remotely to the C24 Inter-
active Servers.
NOTE: The C24-HUB is an interface device which connects to security panels, IP cameras, sensors, Z-wave based home automation devices, etc. to deliver a
host of advanced functionality.
NOTE: Life-style events are “non alarm” events. Life-safety events are “alarm” events.
The following features are available with the RS-422 C24 Interactive:
Communicator faults can be transmitted. 
Panel communication errors are reported to the C24-HUB.
Real time reporting of Zone status information to the C24 Interactive Server.
Remote update of the Communicator (flash upgrade).
SMS incoming “wake up” for the 3G/GPRS channel.
WEB login to request an incoming session with the Communicator.
Zone Label Programming. 
NOTE: Communicator buffers 1000 date/time stamped Life-Style events to the C24-HUB as First In First Out (FIFO). 
Encryption
The Communicator uses 128 Bit AES Encryption. Encryption can only be enabled from the monitoring station receiver. Each receiver (Ethernet 1 and 2, 3G/
GPRS 1 and 2) can independently have encryption enabled or disabled. When encryption is enabled, the central station will configure the device to encrypt
communications the next time the Communicator module performs a communication to that receiver. 
NOTE: Packets will start being encrypted only after the next event is sent to that receiver, or if the unit is restarted.
Before leaving the installation site, the Communicator TL260R/TL2603GR Ethernet line shall be connected via an APPROVED (acceptable to the local 
authorities) Network Interface Device (NID) (e.g., for UL Installations, UL60950 listed NID). All wiring shall be performed according to the local electrical 
codes.
This 3G/GPRS/Ethernet Communicator shall be installed by Service Persons only. (Service Person is defined as a person having the appropriate technical training
and experience necessary to be aware of hazards to which that person may be exposed in performing a task and can also take measures to minimize the risks to that
Table 1: Communicator Ratings
Model
3G2060R 
3G/GPRS only
TL260R
Ethernet only
TL2603GR
Ethernet and 3G/GPRS 
POWER SUPPLY RATINGS
• Input Voltage
Nominal 12 VDC: 
The panel Bell output shall be derated:
700mA - (Communicator mA) = (derated Bell output). 
CURRENT CONSUMPTION
• Standby Current
90mA @ 13.66V
100mA @ 13.65V
120mA @ 13.66V
• Alarm (Transmitting) Current
400mA @ 12V
• Operating Frequency
Quad band 850MHz, 900MHz, 1800MHz, 1900MHz
• Typical Antenna Gain
2dBi
ENVIRONMENTAL SPECIFICATIONS
• Operating Temperature
 32°F - 120°F (0°C - 49°C) 
• Humidity
5% ~ 93% relative humidity, non-condensing
MECHANICAL SPECIFICATIONS
• Board Dimensions (mm)
100 × 150 × 15 
100 × 150 × 18 
100 × 150 × 15 
• Weight (grams) with bracket
310 290  320 
Table 2: Compatible Receivers, and Panels
Communicator
Receiver/
Panel 
Description
3G2060R
TL260R
TL2603GR
Receiver
• Sur-Gard System I Receiver, version 1.13+
• Sur-Gard System II Receiver, version 2.10+
• Sur-Gard SG-DRL3-IP, version 2.30+ (for Sur-Gard System III Receiver)
• Sur-Gard SG-DRL4-IP version 1.20+ (for Sur-Gard System IV Receiver)
Panel
• Power Series PC1616, version 4.5+
• Power Series PC1832, version 4.5+
• Power Series PC1864, version 4.5+
P