Visonic Inc. DUO220EAM ユーザーズマニュアル

ページ / 4
3.5 The Power-up Process
 
3.6 What Happens in Case of Masking?
 
After connecting the (+) and (–) terminals to the power source, 
the DUO 220 starts a 60-second warm-up period, indicated by 
alternate flashing of both LEDs. 
If an attempt is made to stick masking material over the lens or 
put a masking object close to the lens (DUO 220AM only), a 
trouble alert will result about 60 seconds after masking: 
Caution! If the alternate flashing of the LEDs does not stop within 
60 seconds, a failure has been detected by the self-test circuitry 
or, if you are dealing with DUO 220AM, the unit may be masked 
(see Para. 3.6). 
•  The red and green LEDs will flash alternately; 
•  The TRB output will pull to ground and will remain grounded 
until the detector is reset (see Para. 5.6 for procedure). 
 
4. INDICATORS AND SELECTORS  
4.2 Mode Selector 
4.1 LED Indications 
The DIP switch mode selector is mounted on the unit’s PC board 
(see Fig. 3). It controls four functions as demonstrated in Fig. 6 
and as detailed in Table 2.  
The two LEDs (Fig. 1) are used to signal various alarm and 
trouble messages as shown in Table 1 below: 
Table 1. Interpreting the LED Indications 
 
State of LEDs 
 
 
GREEN RED Significance 
Off Off 
No 
detection 
On 
Off 
MW walk-test detection 
Flashes 
Off 
PIR walk-test detection 
Off 
On 
Alarm: MW + PIR detection 
Flashes Flashes 
Trouble (or masking) is being 
detected by the self test circuitry, or 
Initial warm-up routine (stops 60 
seconds after power up). 
Figure 6. DIP Switch Mode Selector 
Table 2. Mode Selector Switch Functions 
Switch State  Function 
Default 
SW-1 OFF 
ON 
One motion event trips the PIR 
Two motion events trip the PIR 
ON 
SW-2 OFF 
ON 
Alarm walk test is disabled
Alarm walk test is enabled 
ON 
SW-3 OFF 
ON 
MW/PIR walk test is disabled 
MW/PIR walk test is enabled 
ON 
SW-4 OFF 
ON 
Output relay opens upon alarm 
Output relay opens upon alarm 
and/or when trouble is detected. 
OFF 
Notes: 1. During walk testing, the first LED to respond is the 
green one. It illuminates steadily (MW detection) or flashes (PIR 
detection), depending on which one of the two detectors 
discovered the motion first. Upon subsequent discovery of the 
motion by the other detector, the green LED will go off and the 
red LED will illuminate (alarm). 
2. If the green and red LEDs continue to flash beyond the warm-
up period, a malfunction or masking has been diagnosed. 
Replace the unit without delay. 
*Setting SW-2 and SW-3 to OFF does not disable the trouble 
indication (flash/flash). 
5. Initial Adjustments   
5. ADJUSTMENT AND TEST  
5.1  Adjusting the Vertical Angle 
For faster catch performance, shift SW-1 to OFF. In this position, 
only one motion event is required to trip the PIR detector. 
The vertical adjustment scale for the PIR detector is located at 
the lower left edge of the PC board (see Figure 3). A screw in the 
middle of the board allows fast and easy adjustment from +2° to 
–12°. All DUO 220 units are pre-adjusted in the factory to –5°.  
5.3  PIR Walk Test 
A.  Rotate the MW RANGE control all the way towards MIN. 
Table 3 below provides recommended vertical adjustment angles 
for various combinations of mounting height and coverage range.  
B.  Verify that DIP switch SW-3 is set to ON (the green walk-test 
LED is enabled). 
A.  Use Table 3 to find the optimum angle for the coverage you 
require. For example, if a coverage range of 9 m (30 ft) is 
required and the detector is installed at a height of 1.8 m (6 ft) 
above the floor, set the vertical angle to -6°. 
C.  Mount the front cover in place. 
D.  Walk into the detector's field of view at the expected far edge 
of the coverage area. The green LED should flash for up to 5 
seconds each time your motion is detected.  
Table 3. Vertical Angle Adjustment  
 
Note:  If the green LED illuminates steadily, your motion has 
been detected by the MW detector. 
 
E.  If PIR detection is not obtained at the far end of the coverage 
area, remove the front cover and re-adjust the vertical angle. 
Replace the cover and retest. 
5.4  MW Walk Test  
A.  Remove the front cover. 
B.
  Verify that the MW range control is set to MIN and DIP switch 
SW-3 is set to ON (the green walk-test LED is enabled). Close 
cover. 
B. Loosen the vertical adjustment screw, slide the PC board 
along the vertical slot until the pointer indicates the required 
angle on the scale. Then tighten the adjustment screw firmly. 
C. Start by moving into the coverage area at the far edge. The 
green LED should light steadily for up to 5 seconds each time 
your motion is detected. 
 Note: 
Since the adjustment screw also fastens the PC board 
to the base, vertical adjustment should be repeated if the PC 
board is replaced.  
D. If your motion was not detected at the far edge of the 
coverage area, advance the MW RANGE control slightly 
toward MAX and try again until your motion is detected 
reliably at the far edge. 
5.2  Setting the Motion Event Counter
 
If you wish to set the PIR detector for maximum false alarm 
immunity, shift DIP switch 1 (SW-1) to ON. In this position, two 
consecutive motion events are required to trip the PIR detector. 
Caution! The MW detection range must not exceed the far 
edge of the desired coverage area.  
DE1823