Visonic Inc. DUO220EAM ユーザーズマニュアル
3.5 The Power-up Process
3.6 What Happens in Case of Masking?
After connecting the (+) and (–) terminals to the power source,
the DUO 220 starts a 60-second warm-up period, indicated by
alternate flashing of both LEDs.
If an attempt is made to stick masking material over the lens or
put a masking object close to the lens (DUO 220AM only), a
trouble alert will result about 60 seconds after masking:
Caution! If the alternate flashing of the LEDs does not stop within
60 seconds, a failure has been detected by the self-test circuitry
or, if you are dealing with DUO 220AM, the unit may be masked
(see Para. 3.6).
• The red and green LEDs will flash alternately;
• The TRB output will pull to ground and will remain grounded
• The TRB output will pull to ground and will remain grounded
until the detector is reset (see Para. 5.6 for procedure).
4. INDICATORS AND SELECTORS
4.2 Mode Selector
4.1 LED Indications
The DIP switch mode selector is mounted on the unit’s PC board
(see Fig. 3). It controls four functions as demonstrated in Fig. 6
and as detailed in Table 2.
The two LEDs (Fig. 1) are used to signal various alarm and
trouble messages as shown in Table 1 below:
Table 1. Interpreting the LED Indications
Table 1. Interpreting the LED Indications
State of LEDs
GREEN RED Significance
Off Off
Off Off
No
detection
On
Off
MW walk-test detection
Flashes
Off
PIR walk-test detection
Off
On
Alarm: MW + PIR detection
Flashes Flashes
Trouble (or masking) is being
detected by the self test circuitry, or
Initial warm-up routine (stops 60
Initial warm-up routine (stops 60
seconds after power up).
Figure 6. DIP Switch Mode Selector
Table 2. Mode Selector Switch Functions
Switch State Function
Default
SW-1 OFF
ON
One motion event trips the PIR
Two motion events trip the PIR
Two motion events trip the PIR
ON
SW-2 OFF
ON
Alarm walk test is disabled
*
Alarm walk test is enabled
ON
SW-3 OFF
ON
MW/PIR walk test is disabled
MW/PIR walk test is enabled
MW/PIR walk test is enabled
ON
SW-4 OFF
ON
Output relay opens upon alarm
Output relay opens upon alarm
and/or when trouble is detected.
OFF
Notes: 1. During walk testing, the first LED to respond is the
green one. It illuminates steadily (MW detection) or flashes (PIR
detection), depending on which one of the two detectors
discovered the motion first. Upon subsequent discovery of the
motion by the other detector, the green LED will go off and the
red LED will illuminate (alarm).
2. If the green and red LEDs continue to flash beyond the warm-
2. If the green and red LEDs continue to flash beyond the warm-
up period, a malfunction or masking has been diagnosed.
Replace the unit without delay.
*Setting SW-2 and SW-3 to OFF does not disable the trouble
indication (flash/flash).
indication (flash/flash).
5. Initial Adjustments
5. ADJUSTMENT AND TEST
5.1 Adjusting the Vertical Angle
For faster catch performance, shift SW-1 to OFF. In this position,
only one motion event is required to trip the PIR detector.
only one motion event is required to trip the PIR detector.
The vertical adjustment scale for the PIR detector is located at
the lower left edge of the PC board (see Figure 3). A screw in the
middle of the board allows fast and easy adjustment from +2° to
–12°. All DUO 220 units are pre-adjusted in the factory to –5°.
5.3 PIR Walk Test
A. Rotate the MW RANGE control all the way towards MIN.
Table 3 below provides recommended vertical adjustment angles
for various combinations of mounting height and coverage range.
B. Verify that DIP switch SW-3 is set to ON (the green walk-test
LED is enabled).
A. Use Table 3 to find the optimum angle for the coverage you
require. For example, if a coverage range of 9 m (30 ft) is
required and the detector is installed at a height of 1.8 m (6 ft)
above the floor, set the vertical angle to -6°.
C. Mount the front cover in place.
D. Walk into the detector's field of view at the expected far edge
D. Walk into the detector's field of view at the expected far edge
of the coverage area. The green LED should flash for up to 5
seconds each time your motion is detected.
Table 3. Vertical Angle Adjustment
Note: If the green LED illuminates steadily, your motion has
been detected by the MW detector.
E. If PIR detection is not obtained at the far end of the coverage
area, remove the front cover and re-adjust the vertical angle.
Replace the cover and retest.
5.4 MW Walk Test
A. Remove the front cover.
B. Verify that the MW range control is set to MIN and DIP switch
B. Verify that the MW range control is set to MIN and DIP switch
SW-3 is set to ON (the green walk-test LED is enabled). Close
cover.
B. Loosen the vertical adjustment screw, slide the PC board
along the vertical slot until the pointer indicates the required
angle on the scale. Then tighten the adjustment screw firmly.
C. Start by moving into the coverage area at the far edge. The
green LED should light steadily for up to 5 seconds each time
your motion is detected.
Note:
Since the adjustment screw also fastens the PC board
to the base, vertical adjustment should be repeated if the PC
board is replaced.
D. If your motion was not detected at the far edge of the
coverage area, advance the MW RANGE control slightly
toward MAX and try again until your motion is detected
reliably at the far edge.
5.2 Setting the Motion Event Counter
If you wish to set the PIR detector for maximum false alarm
immunity, shift DIP switch 1 (SW-1) to ON. In this position, two
consecutive motion events are required to trip the PIR detector.
immunity, shift DIP switch 1 (SW-1) to ON. In this position, two
consecutive motion events are required to trip the PIR detector.
Caution! The MW detection range must not exceed the far
edge of the desired coverage area.
DE1823
3