Climax Technology Co Ltd CO ユーザーズマニュアル

ページ / 4
 
1
CO-8ZW Carbon Monoxide Detector 
 
Introduction 
CO-8 is a Carbon Monoxide Detector. It is capable of sending wireless signals to the Z-Wave 
Gateway/Control Panel upon detection of Carbon Monoxide concentration. 
The Carbon Monoxide Detector is a Z-Wave enabled device and is fully compatible with any Z-Wave 
enabled network. 
Z-Wave is a wireless communication protocol that uses a low-power RF radio. By taking advantage of 
the Z-Wave mesh network, commands can be transmitted to their destination via intermediary “listening” 
Z-Wave products. 
 
Parts Identification 
1. Dual Color LED indicator (Amber/Red) 
The LED indicator lights up in the following conditions: 
- Red LED flashes twice   
The Carbon Monoxide Detector has successfully included 
(learnt) into Z-Wave Gateway/Control Panel. 
- Red continuous flash: 
The Carbon Monoxide Detector is activated. 
- Amber LED flashes every second: 
The Carbon Monoxide Detector is in Alarm Silence mode. 
2. Function Button 
- Press the button once to send a supervision signal. 
- Press the button once during alarm to silence the alarm. 
- Press and hold the button 3 times within 1.5 seconds to send a 
learn code. 
- Press and hold the button for 10 seconds to factory reset. 
3. Battery Compartment 
The Carbon Monoxide Detector is powered by three 
AA Alkaline 1.5V batteries. 
4. Mounting Hole 
5. Mounting Bracket 
 
Features 
z
z
 
 
C
C
a
a
r
r
b
b
o
o
n
n
 
 
M
M
o
o
n
n
o
o
x
x
i
i
d
d
e
e
 
 
D
D
e
e
t
t
e
e
c
c
t
t
i
i
o
o
n
n
 
 
 
 
 
 
The Carbon Monoxide Detector will be activated according to the following table when CO 
concentration is detected. 
CO concentration 
level 
Time taken before 
alarming 
30 ppm 
None 
50 ppm 
60-90 minutes 
100 ppm 
10-40 minutes 
300 ppm 
Under 3 minutes 
Once the CO concentration level exceeds the threshold and persists for the time length as 
listed in the above table, the Carbon Monoxide Detector will transmit the signal to the Z-Wave 
Gateway/Control Panel and raise alarm with its built-in siren. 
After the alarm has been activated, the Carbon Monoxide Detector will continue to send the 
alarm signal every 2 minutes as long as CO concentration remains above 30 ppm. 
If the CO concentration drops below 30 ppm, the Carbon Monoxide Detector will stop alarming 
and transmit a restore signal