RS485 COMMUNICATION AND 
TERMINATION SETTING 
Both IdentIPoint readers and IOMs are 
equipped with a termination circuit and 
do not need an external termination 
resistor. Setting the DIP switch 2 on S1 
to ON introduces a termination resistor 
on the RS485 line. The units that sit 
physically on both ends of an RS485 
bus should have their RS485 
termination turned on. It is also 
recommended to turn on the pull-up and 
pull-down resistors in the IdentIPoint 
reader (master)
 
 
 
 
 
 
 
 
 
 
 
Termination OFF
Termination ON
Termination ON
IOM (Slave 1)
Termination OFF
Reader (Master)
Termination ON
Pull-up ON
Pull-down ON
IOM (Slave 2)
Termination ON
Termination OFF
Termination ON
Termination ON
IOM (Slave 1)
Termination OFF
Reader (Master)
Termination ON
Pull-up ON
Pull-down ON
IOM (Slave 2)
Termination ON
Termination OFF
Termination ON
Termination ON
IOM (Slave 1)
Termination OFF
Reader (Master)
Termination ON
Pull-up ON
Pull-down ON
IOM (Slave 2)
Termination ON
Termination ON
Termination OFF
Termination ON
IOM (Slave 1)
Termination OFF
Reader (Master)
Termination ON
Pull-up ON
Pull-down ON
IOM (Slave 2)
Termination ON
Fig.27. DIP Switch S1 settings on reader and IOMs for RS485 
termination
95-7771  