Digital Monitoring Products Inc PC0104 ユーザーズマニュアル

ページ / 4
1184 Detector Installation Guide 
Digital Monitoring Products
3
Installing or Replacing the Batteries
Observe polarity when installing the battery.  Use only 3.0V lithium batteries,  DMP Model CR123-FIRE or Panasonic 
Model CR123A-Fire.    
Note: When setting up a wireless system, it is recommended to program zones and connect the receiver before 
installing batteries in the transmitters.
1.  Remove the detector from the mounting base by grasping the detector and turning it counterclockwise 
approximately 15 degrees. The detector should snap off of the mounting base.
2.  The battery is located on the inside of the cover 
2.  If replacing the battery, remove the old battery and dispose of them properly.
3.  Observing correct polarity, insert the new 3V lithium battery into the battery compartment and replace the 
cover.  Use only new batteries when replacing old ones.
4.  Reattach the detector to the mounting base.  See Attaching and Removing the Detector.
5.  Test the detector.  See Testing the Detector.
  Caution: Properly dispose of used batteries. Do not recharge, disassemble, heat above 212°F (100°C), or 
  incinerate.   Risk of fire, explosion, and burns.
Testing the Detector Alarm
1.  To test the detector alarm, enable Walk Test operation on the control panel.  If the system is monitored, the 
system sends a System Test Begin report (System message S66) to the central station.  
 
To conduct the Walk Test, reset the control panel by momentarily placing a jumper on J16.  From the keypad, 
enter the code 8144. The keypad displays WALK TEST.  Refer to the panel programming guide for complete 
information on Walk Test operation.
2.  For the XTL or XT30/XT50 Series panels, select STD (Standard Walk Test).  
For the XR100/XR500 Series panels, select FI (Fire zones).  A sensor reset occurs after each detector tested.
3.  Remove the detector from the mounting base.  See Attaching and 
Removing the Detector.  Carefully short the two terminals (screw heads) 
momentarily to send an alarm signal to the control panel.  Verify that 
the walk test trip counter increments to indicate a successful test.  
Once testing is completed, install the detector back onto the mounting 
base.  Shorting the terminals does not affect the standard operation of 
the detector.
4.  Select END to stop the Walk Test.  When the Walk Test ends or a 
20-minute time-out expires, a final Sensor Reset occurs. The System Test 
End message (System message S67) is sent to the central station along 
with verify and fail messages for each zone under test.  Faulted zones 
then display on the keypad.
Important: The control panel alarm and all auxiliary functions should be 
verified for a complete test of the system.  See the panel programming guide 
for additional information.
Battery Life Expectancy
Typical battery life expectancy for DMP wireless heat detectors is at least 2 years.  DMP wireless equipment uses 
two-way communication to extend battery life.  
The following situations can reduce battery life expectancy:
•  If a receiver is unplugged or not installed.
•  Frequent transmissions, such as how often the detector is tested.
•  When installed in extreme hot or cold environments.
Figure 5: Testing the Detector