Digital Monitoring Products Inc PC0117 ユーザーズマニュアル
XTL Installation Guide
Digital Monitoring Products
7
InstallatIon
Wireless Keypads
11.1 Mounting Keypads
DMP keypads have removable covers that allow the base to be mounted on a wall or other flat surface using
the screw holes provided on each corner.
11.2 Wireless Keypad Association
Pressing the reset button 3 times within 5 seconds enables the keypad association mode. For one minute
the panel listens for wireless keypads. Any keypads not already associated with another panel are accepted.
The first keypad detected is assigned to the first open keypad address. Keypads are automatically assigned
addresses based upon the order in which they are detected. A maximum of 4 keypads may be associated
with a panel.
11.3 Existing Keypad Confirmation
During the one minute time period, the panel also confirms that programmed keypads are still functioning.
Wireless Zones
12.1 Description
XTL panels provide 28 wireless zones numbered 1 to 28. The default zone names are described below.
Zone Number
Zone Name
Zone Type
Area Assignment
1
FRONT DOOR
EX
PERIM
2
BACK DOOR
EX
PERIM
3
INTERIOR DOOR
NT
INT
4
UPSTAIRS DOOR
EX
PERIM
5
BASEMENT DOOR
EX
PERIM
6
GARAGE DOOR
EX
PERIM
7
WAREHOUSE DOOR
EX
PERIM
8
SHIPPING DOOR
EX
PERIM
9
BREAKROOM DOOR
NT
INT
10
STOCKROOM DOOR
NT
INT
11
FRONT MOTION
NT
INT
12
BACK MOTION
NT
INT
13
INTERIOR MOTION
NT
INT
14
UPSTAIRS MOTION
NT
INT
15
BASEMENT MOTION
NT
INT
16
GARAGE MOTION
NT
INT
17
GLASSBREAK
NT
INT
18
WATER DETECTOR
AUX 1
INT
19
LOW TEMPERATURE
AUX 1
INT
20
SMOKE DETECTOR
FI
21
FRONT SMOKE
FI
22
BACK SMOKE
FI
23
INTERIOR SMOKE
FI
24
UPSTAIRS SMOKE
FI
25
BASEMENT SMOKE
FI
26
GARAGE SMOKE
FI
27
WAREHOUSE SMOKE
FI
28
SHIPPING SMOKE
FI