Dust  covers  are  an  effective  way  to  limit  the  entry  of  dust  into  the 
smoke detector sensing chamber during construction. However, they 
may not completely prevent airborne dust particles from entering the 
detector. Therefore, it is recommended that the detectors be removed 
before beginning construction or other dust producing activity. When 
returning  the  system  to  service,  be  sure  to  remove  the  dust  covers 
from any detectors that were left in place during construction.
Smoke detectors are not to be used with detector guards unless the 
combination has been evaluated and found suitable for that purpose.
Tamper Protection
This detector has a built-in tamper switch that will cause a CHECK 
signal  to  be  displayed  at  the  console  of  the  alarm  system  if  it  is 
removed  from  its  mounting  base.  The  5808W3  detector  includes  a 
tamper-resistant  feature  that  prevents  removal  from  the  mounting 
base without the use of a tool. To engage the tamper-resistant feature, 
cut the small plastic tab located on the mounting base (Figure 2), and 
then install the detector. To remove the detector from the base once it 
has been made tamper resistant, use a small screwdriver to depress 
the square tamper release tab, located on the skirt of the mounting 
base, and turn the detector counterclockwise.
Testing the Sensor
NOTE:  Before  testing,  notify  the  central  station  that  the  smoke 
detector  system  is  undergoing  maintenance,  in  order  to  prevent 
unwanted alarms.
During initial power-up, do not use SENS-RDR or canned smoke to 
test  the  detector.  The  SENS-RDR  and  canned  aerosol  can  be  used 
after  power-up  sequence  has  completed.  Detectors  must  be  tested 
after  installation  and  following  periodic  maintenance.  The  5808W3 
may be tested as follows:
A. Test Switch
1.   A  recessed  test  switch  is  located  on  the  detector  housing  (see 
Figure 4).
2.   Push  and  hold  the  recessed  test  switch  for  a  minimum  of  5 
seconds.  Use  a  small  screwdriver  or  Allen  key  with  maximum 
diameter of 0.18 inch (the alarm panel will trigger and then the 
smoke detector will go into alarm. If the tool is removed from the 
recessed switch the sounder will shut off.)
 
 If the detector is within the listed sensitivity limits, the LED on 
the  detector  should  blink  once  per  second  and  the  horn  should 
sound within 3 seconds.
POSITION SENS-RDR AT AN ANGLE ON 
THE OVAL AREA OR AT THE CHAMBER 
OPENING BY THE WORD “PAINT”
RECESSED 
TEST 
SWITCH
LED
PUSH RECESSED 
SWITCH WITH A 
0.18˝ MAX. 
DIAMETER TOOL
S0308-00
Figure 4. Recessed Test Switch Opening and SENS-RDR Position
B. Smoke Entry Test
A canned smoke agent may be used to test the detector. Refer to the 
manufacturer’s instructions for proper use of the canned smoke. HSI 
brand canned smoke has been tested and approved for use with this 
type of smoke detector.
C. Direct Heat Method (Hair dryer of 1000-1500 watts)
Direct  the  heat  toward  either  side  thermistor.  Be  sure  to  hold  the 
heat source about 12 inches from the detector to avoid damage to the 
plastic. The detector will reset only after it has time to cool.
Smoke  detection  testing  is  recommended  for  verifying  system 
protection capability.
A detector that fails to activate with any of these tests should first be 
cleaned as outlined in this manual’s MAINTENANCE section. If the 
detector still fails to activate, return for repair.
Testing Signal Strength
NOTE: Remove battery tab before installation. 
This test should be performed in accordance with NFPA 72 inspection, 
testing  and  maintenance  requirements  to  determine  a  strong 
communication path with the control panel.
1.   Activate  the  wireless  system’s  GO/NO  GO  TEST  mode  from 
the keypad.
2.   Depress  and  hold  the  smoke  detector’s  TEST  switch.  If  the 
detector  has  not  previously  detected  a  low  battery  condition 
and  it  is  within  proper  sensitivity  limits,  the  detector  should 
immediately  transmit  an  alarm  signal  to  the  control  panel. 
The  built-in  horn  will  start  to  sound  about  2.5  seconds  after 
depressing the button.
3.   The wireless system’s keypad should emit at least three audible 
sounds when the alarm transmission is received and will display 
the transmitting detector’s zone number.
4.   When the console has received the test signal, release the TEST 
switch. The horn will immediately stop and a few seconds later 
the detector’s zone number will clear from the console display.
5.   If the console does not respond as noted, check the polarity of the 
battery  and  be  sure  it  is  fresh.  If  this  is  an  initial  installation, 
try moving the detector to another location that provides proper 
reception. Also be sure that the detector has been “enrolled” by 
the control panel (see PROGRAMMING). Then, repeat the test.
6.   Turn  off  the  system’s  TEST  mode  from  the  keypad  (security 
code + OFF).
Testing Programmed Loops
This  test  should  be  performed  before  installation  to  ensure  that  all 
loops intended to be used have been programmed and are operational 
in the system.
1.   Activate the system’s TRANSMITTER ID SNIFFER mode from 
the keypad (see the control panel’s instructions). All programmed 
wireless  zones  will  be  displayed,  one  by  one,  on  the  system 
keypad.  Make  sure  all  smoke  detector  zones  are  displayed  in 
the sequence. (If they are not, recheck that all zones have been 
properly programmed.)  
2.   With  the  detector  mounted  to  the  bracket,  press  the  smoke 
detector’s  TEST  switch.  All  zones  associated  with  the  smoke 
detector  should  disappear  from  the  keypad  on  the  next  display 
cycle.  This  means  that  the  system  has  received  a  transmission 
from each loop you programmed.
3.   When testing is complete, enter the Installer code + the OFF key 
to exit TEST mode.
When all system testing has been completed, notify the central station 
that the system is back on line.