INSTALLATION and SETUP GUIDE 
 
 
GENERAL INFORMATION 
The 6160VPADT is an addressable remote Voice 
Touchpad with a built-in Proximity Reader, designed 
for use with ADT control panels.  This Touchpad 
provides the following features:   
•  Backlit Display (programmable as permanent on 
some controls) 
•  Continuously Backlit Touchpad Keys 
•  Programmable Function Keys 
•  Built-in Sounder 
•  Arm/Disarm via Prox Tag 
•  Voice Chime 
•  Voice Status 
•  Message Center 
•  Supervised by control panel (if supported). 
Installation Notes 
•  The Touchpad can only be used on addressable 
systems and cannot be used on Control Panels that 
use Keypad Address 31. The Touchpad must be set 
for address 00-30. When used with the Safewatch 
Pro/Security Manager 3000 control panels, address 16 must 
be assigned to the first Touchpad.  Additional Touchpads 
must be assigned to addresses 17 – 23. (Refer to Setting the 
Touchpad Options.) 
•  The Prox reader utilizes an additional keypad address, 
which must be enabled at the Control Panel (see control 
panel installation instructions for allowable keypad 
addresses). 
•  The partition used for the Touchpad, Prox Reader, and User 
Code must be the same. 
•  The Prox Tags will only arm and disarm one partition. The 
Prox Reader cannot be used to perform global arming 
operations. 
•  Presenting a Prox Tag is functionally equivalent to entering 
a 4 digit user code. 
•  Voice Chime should only be enabled when used with control 
panels that support the "chime by zone" mode (e.g., 
SAFEWATCH PRO/SECURITY MANAGER 3000).  This 
mode must be enabled at the control panel.  Refer to the 
control panel's installation and setup guide for information 
on how to program the chime mode.  
 
6160VPADT QUICK SETUP 
The following steps can be used to install the 6160VPADT Remote Touchpad and Prox Reader. For more detailed information 
regarding installation, programming and operation, refer to Detailed Information and Installation. 
 
When installing wiring between the Touchpad’s terminal block and the terminal block on the Control Panel, connect only the 
red and black Aux. Power connections at the Touchpad initially, and follow the step-by-step instructions for addressing the 
Touchpad and Prox Reader. 
 
Step Action 
1. 
Connect red and black wires only to touchpad. 
2. 
Program the keypad address. (Safewatch Pro 3000 = 16) 
3. 
Press * to save. 
4. 
At the “VOICE CHIME” prompt, press *. 
5. 
At the “ADDITIONAL CON” prompt, enter “0” if this is the Primary Voice Touchpad, or “1” if this is an additional 
Voice Touchpad. 
6. 
Press * to save.  
7. 
The “Prox Addr? XX” will be displayed. Enter an unused keypad address. 
8. 
Press * to save. 
9. 
Power down the panel. 
10. 
Connect the green and yellow wires. 
11. 
Power up the panel. 
12. 
In panel programming, configure the Prox Reader Address that you just programmed as a keypad. 
a.  If you are using a Vista-128, Vista-50 or like panels, go to device programming and program the Prox Address 
as an “Alpha Console.” 
b.  If you are using a Safewatch Pro 3000, use an address between 17 and 23. 
 
Go to location *190 to *196 and enter the partition in which the Touchpad is being used. 
13. Exit 
programming. 
14. 
Enroll the Prox Tag by programming a new “User” code with the four-digit serial number located on the tag’s 
packaging. 
 