Combination Smoke/Carbon Monoxide (CO) Detector / Combinación de detector de Humo/Monóxido de carbono (CO) 
Quick Installation Guide 
Guía Rápida de Instalación
 
 
This device is intended for use with Honeywell controls that support SiX series 
devices including the SiXCOMBO. Check the control for compatibility with this 
device. This device occupies 3 control panel zones, one zone for each service 
(smoke detection, heat detection, carbon monoxide detection). 
 
FEATURES 
  Multi-Criteria Sensing: 
uses four sensing elements to react faster while 
minimizing false alarms: 
  - Photoelectric smoke sensor detects airborne smoke particles 
  - Carbon Monoxide (CO) sensor detects smoldering fires 
  - Infrared (IR) sensor measures ambient light and flame signatures, such as 
flame flicker 
  - Thermal detection monitors for dangerous rise in temperature 
  CO Detector End-of-Life reporting (detector needs replacing) 
  Smoke detector maintenance reporting (detector needs cleaning or replacing) 
  Low Battery Detection 
  One Go / All Go: all smoke/CO detectors in the system programmed as one-go-
all-go will sound on alarm. 
  Voice announcements (English only)
 
 
See Installation Instructions (800-22142 – https://mywebtech.honeywell.com/) and 
the Limitations of Fire Alarm Systems Insert (800-15144 12/15) and System Smoke 
Detectors Application Guide (SPAG9101 7/12). 
 
LED INDICATORS
 
The SiXCOMBO Smoke/CO detector has a multi-color top LED:   
Green =  Supervisory indication; blinks during power on, reset, and during normal 
operation 
Amber =  Signal maintenance and trouble events 
Red =   Alarm condition (either Smoke or CO) 
Side LED windows indicate alarms:  
Red = smoke alarm 
Blue = CO alarm
 
 
 
 
 
 
 
 
 
 
 
Este producto está diseñado para ser usado en controladores Honeywell que 
soportan dispositivos de la serie SiX including the SiXCOMBO. Check the control for 
compatibility with this device. This device occupies 3 control panel zones, one zone 
for each service (smoke detection, heat detection, carbon monoxide detection).
 
 
 
CARACTERISTICAS  
  Detección multi-criterio: Utiliza cuatro elementos de detección para una más 
rápida reacción mientras se minimizan falsas alarmas:
 
  - Sensores fotoeléctricos de humo que detectan partículas de humo en el aire 
  - Sensores de detección de Monóxido de Carbono (CO) para detección de 
incendios sin llama 
  - Sensores infrarrojos (IR) que detectan luces de ambiente y señales de flamas 
tales como movimiento de las llamas 
  - Detección termal que monitorea aumento peligroso de temperaturas 
 
Fin de vida útil del detector de CO (el detector necesita ser remplazado) 
 
Reporte de mantenimiento del sensor de humo (Cuando el sensor requiere limpieza 
or replacing) 
  Detección de batería baja. 
  Uno se activa / Todos se activan: todos los detectores de humo/CO en el sistema 
programados como “uno se activa/todos se activan”, sonarán su propia alarma 
  Voice announcements (English only) 
 
Vea la guía de instalación de Honeywell (800-22142- 
https://mywebtech.honeywell.com/) y el inserto de las limitaciones de sistemas de 
alarma de fuego. (800-15144SP 12/15). Consulte la Guía de aplicación de detectores 
de humo del sistema (SPAG9101 7/12).
 
 
INDICADORES DE LED
 
El detector de humo/Monóxido de carbono SiXCOMBO contiene un LED multicolor:  
Verde = Indicador de supervisión; parpadea durante iniciación, reinicio y durante 
operación normal. 
Ámbar = Señal de eventos de mantenimiento o problemas 
Rojo = Condición de alarma (de humo o monóxido de carbono) 
Ventanas de LED laterales: Rojo = Humo, Azul = Monóxido de carbon
 
 
ENROLLMENT
 
REGISTRO
  
IMPORTANT NOTES:  
 The Smoke, Heat, and Carbon Monoxide (CO) sensors each 
have unique MAC ID numbers (serial numbers) that are 
enrolled in separate zones. 
 Once enrolled, the device cannot be used with another system 
until it is removed from the current controller. See the 24-hour 
Enrollment Deletion section below or the controller’s 
instructions. 
 
Enroll the Device Services (Smoke, Heat, CO) 
1. Remove the detector from the base plate (tamper switch 
must be faulted when enrolling). 
2. Put the control panel in Zone Programming mode. 
  For Lyric Controller: 
Security > installer code > Program 
> (
scroll down) > SiX Programming 
3. Pull the battery tab to activate enrollment process (be sure 
batteries are seated properly to avoid a false low battery 
condition). If the battery tab has already been removed and 
the unit is powered up, press either Test switch for less 
than 3 seconds to activate the enrollment process. 
4. The device attempts enrollment (green LED flashes about 8 
seconds). If successful, the green LED lights steady for 3 
seconds and the device announces successful enrollment. 
  If the LED does not light steady, enrollment failed. Retry by 
pressing either Test switch for less than 3 seconds. 
  All services (Smoke, Heat, and CO) are automatically 
enrolled in sequential (or next available) zone numbers with 
the following default attributes: 
Zone 
Device Type 
Zone Response Type 
Smoke Det.  Smoke Detector 
Fire No Verification 
Heat Det. 
Heat Sensor 
Fire No Verification 
CO Det. 
Carbon Mono. Det.  Carbon Monoxide 
 
 
NOTE: Maintenance and CO End-of-Life are automatically 
enrolled for the respective smoke and CO zones. Upon 
either of these conditions, Contact ID code E386 “Low 
Maintenance Smoke” is sent for the respective zone. 
 
Supervision: Detector supervision is factory set for 1 
minute and is not programmable. 
 
5. To assign zone descriptors for each of the zones and/or 
change device type or zone response type, select the zone 
then select 
Edit and make the desired changes. Press 
Save when done. 
 
24-Hour Enrollment Deletion 
Use this procedure within 24 hours of initial enrollment to delete 
this device from the controller. This allows reenrollment in a 
specific controller in case enrollment in that controller failed 
(i.e., the device inadvertently enrolled in a different controller). 
This resets the device to factory default settings and removes 
the communication link data in the controller in which it is 
enrolled, allowing the device to be reenrolled in the desired 
controller. 
1.  Press and hold both the Smoke and CO test switches 
simultaneously for 5 seconds, then release. The green light 
flashes rapidly.  
2. Press and hold both buttons again for one second and 
release. 
 
 
 
 
OPEN / ABIERTO
 
 
Operation Modes / Modos de operación 
MODE /  MODO  Status LED (Top) / 
Estado del LED 
LED Windows 
(Side)
 
/ Ventana 
del LED (Lateral)
 
Sounder / 
Sonador 
Speaker / Bocina
 
Power Up / 
Encendido 
Blink Green, every  
2 secs/ Parpadea 
verde cada  
2 segundos 
Dark / 
Apagado 
Silent / 
Silencio 
Voice welcome, 
instructions after 
first time power-up 
or after default 
/ Bienvenida de 
voz, seguido por 
las instrucciones 
POR para la 
selección de 
lenguaje, 
enrolamiento, 
pruebas 
Normal (Standby) 
Estado normal 
Single Blink Green  
every 10 sec / 
parpadeo verde 
cada 10 segundos 
Dark / 
Apagado 
Silent / 
Silencio 
Silent / 
Silencio 
Smoke Alarm / 
Alarma de humo 
Blink Red every 10 
secs / parpadeo rojo 
cada 10 segundos 
Blink Red / 
Parpadeo rojo 
Temp-3 
 “Warning, smoke, 
evacuate”/ 
“Advertencia, 
humo, evacuar”  
Thermal Alarm / 
Alarma termal 
Blink Red every 10    
secs / parpadeo rojo 
cada 10 segundos 
Blink Red / 
Parpadeo rojo 
Temp-3 
“Warning, smoke, 
evacuate”/ 
“Advertencia, 
humo, evacuar” 
CO Alarm / Alarma 
de monóxido de 
carbono 
Blink Red every 10    
secs / parpadeo rojo 
cada 10 segundos 
Blink Blue / 
Parpadeo azul 
Temp-4 
“Warning, carbón 
monoxide, move 
to fresh air” / 
Advertencia, 
monóxido de 
carbón, pasar al 
aire fresco 
Powered Down / 
Apagado 
Dark / 
Apagado 
Dark / 
Apagado 
Silent / 
Silencio 
Silent / 
Silencio 
 
TO SILENCE THE DETECTOR 
Press the test switch. The detector sounds again after 5 minutes if the 
alarm condition continues. 
 
PARA SILENCIAR EL DETECTOR 
Presione el interruptor de prueba. El detector volverá a sonar después 
de 5 minutos si continúa la condición que originó la alarma. 
 
NOTA IMPORTANTE:  
 The Smoke, Heat, and Carbon Monoxide (CO) sensors each 
have unique MAC ID numbers (serial numbers) that are enrolled 
in separate zones. 
 Una vez registrado, el dispositivo no se puede usar con otro 
sistema hasta que sea removido del controlador actual. See the 
24-hour Enrollment Deletion section below or the controller’s 
instructions. 
 
Enroll the Device Services (Smoke, Heat, CO) 
1. Remove the detector from the base plate (tamper switch 
must be faulted when enrolling). 
2. Put the control panel in Zone Programming mode. 
  For Lyric Controller: 
Security > installer code > Program > 
(
scroll down) > SiX Programming 
3. Pull the battery tab to activate enrollment process (be sure 
batteries are seated properly to avoid a false low battery 
condition). If the battery tab has already been removed and 
the unit is powered up, press either Test switch for less than 
3 seconds to activate the enrollment process. 
4. The device attempts enrollment (green LED flashes about 8 
seconds). If successful, the green LED lights steady for 3 
seconds and the device announces successful enrollment. 
  If the LED does not light steady, enrollment failed. Retry by 
pressing either Test switch for less than 3 seconds. 
  All services (Smoke, Heat, and CO) are automatically 
enrolled in sequential (or next available) zone numbers with 
the following default attributes: 
Zone 
Device Type 
Zone Response Type 
Smoke Det.  Smoke Detector 
Fire No Verification 
Heat Det. 
Heat Sensor 
Fire No Verification 
CO Det. 
Carbon Mono. Det.  Carbon Monoxide 
 
 
NOTE: Maintenance and CO End-of-Life are automatically 
enrolled for the respective smoke and CO zones. Upon either 
of these conditions, Contact ID code E386 “Low Maintenance 
Smoke” is sent for the respective zone. 
 
Supervision: Detector supervision is factory set for 1 minute 
and is not programmable. 
 
5. To assign zone descriptors for each of the zones and/or 
change device type or zone response type, select the zone 
then select 
Edit and make the desired changes. Press Save 
when done. 
 
24-Hour Enrollment Deletion 
Use this procedure within 24 hours of initial enrollment to delete 
this device from the controller. This allows reenrollment in a 
specific controller in case enrollment in that controller failed (i.e., 
the device inadvertently enrolled in a different controller). This 
resets the device to factory default settings and removes the 
communication link data in the controller in which it is enrolled, 
allowing the device to be reenrolled in the desired controller. 
1.  Press and hold both the Smoke and CO test switches 
simultaneously for 5 seconds, then release. The green light 
flashes rapidly.  
2. Press and hold both buttons again for one second and 
release. 
 
MOUNTING
 
If the device is not in its final mounting 
location when enrolled, conduct Go/No Go 
tests (see controller’s instructions) to verify 
adequate signal strength. Adjust the device 
location and orientation as necessary. 
 
 
 
MONTAJE
 
Si el dispositivo no está en su ubicación final 
de montaje cuando se registre, realice 
pruebas de Va/No Va (vea las instrucciones 
del controlador) para verificar que la 
intensidad de la señal sea adecuada. Ajuste 
la ubicación y orientación del dispositivo 
según ea necesario.