BEFORE INSTALLATION
Please read this manual thoroughly along with the Application Guides for Sys-
tem Sensor Smoke (A05-1003) and CO Detectors (A05-1099), which provide 
detailed information on detector spacing, placement, zoning and special ap-
plications. Copies of these manuals are available at systemsensor.com.
IMPORTANT:  This detector must be tested and maintained regularly following 
NFPA 72/NFPA 720 requirements. 
GENERAL DESCRIPTION
The W4 series is a battery-operated, system-connected, combination carbon 
monoxide/smoke detector with a built-in wireless transmitter for use with 
iControl wireless control panel models. It will report maintenance, tamper and 
independent smoke alarm or CO alarm signals to a compatible wireless con-
trol panel. It has a speaker for vocal feedback, multi-criteria smoke detection, 
and integrated side LED windows that are viewable from 360 degrees when 
the detector is in an alarm condition.
FEATURES
Smoke Features
•  Multi-criteria smoke sensing using a combination of photoelectric, heat, 
flame flicker and carbon monoxide sensing.
•  Drift compensation and noise rejection algorithms.
•  Smoke test button.
•  360 degree, side viewable red LED smoke indication.
CO Features
•  10 year electrochemical CO sensor.
•  Sensor end-of-life notification. 
•  CO test button.
•  RealTest® functional gas entry test capable.
•  360 degree, side viewable blue LED CO indication.
Audible Annunciation
•  Local integral sounder.
•  Voice speaker provides supplemental instructions during alarm, installa-
tion and maintenance feedback.
Installation and Maintenance
•  Universal mounting base. 
•  Audible maintenance information including smoke sensitivity.
Other Features
•  Ships with 4 CR-123 lithium batteries. 
•  UL/ULC listed to standards 268 and 2075. 
SPECIFICATIONS 
Electrical Specifications
Voltage: 
3 volts DC
Battery Type:  
CR-123 lithium 
Battery Manufacturer: 
Duracell DL123A or Panasonic CR123A  
 
Use of a different battery may have a detrimental effect on device operation 
Number of Batteries: 
Sensitivity 
0.9 to 2.64/ft. (.27 to .80/m)
Audible Signal: 
85dBA
Physical Specifications
Diameter: 
5.95 inches (15.113 cm)
Height: 
2.03 inches (5.1562cm)
Weight: 
13.92oz (383 g)
Operating Temperature Range: 
0 - 38° C (32 - 100°F)
Storage Temperature Range: 
-10 - 70° C (14 - 158° F)
Operating Humidity Range: 
20-95% RH
This product is compatible with iControl Technicolor TCA203 control panels
*NFPA requires a UL listed sounder on the NAC circuit. 
Notice:  This manual shall be left with the owner/user of this equipment.
I56-5942-000
VISIBLE ANNUNCIATON
The W4 series detector has a multi-color top LED; Green, Red, and Amber. 
The LED is green for supervisory indication; it blinks during power on, reset, 
and during normal operation. The LED is amber to signal maintenance and 
trouble events. W4 utilizes the side LED windows to indicate alarm events; 
red for smoke and blue for CO. 
INSTALLATION GUIDELINES
Ceiling: Detector should be at least 12 inches (30 cm) from any wall.
Wall: Detector should be no closer than 6 inches (15 cm) from ceiling.
•  Do not install outdoors or in any environment that does not comply with 
the detector’s environmental specifications.
•  Install in accordance with NFPA 72 and 720 standards.
 
NFPA 72 and 
720 define standards for both commercial and residential installation of 
smoke and CO detectors. Local laws involving CO detection should also 
be considered.
•  If the installation can be interpreted as residential, consult the section 
of NFPA 720 that outlines residential applications.
 
Chapter 9.4.1.1, for 
example, states that carbon monoxide alarms or detectors shall be in-
stalled as follows:
•   Outside each separate dwelling unit sleeping area in the immediate 
vicinity of the bedroom.
•  On every level of a dwelling unit, including basements.
•   Consult NFPA 72, the local Authority Having Jurisdiction (AHJ), and/
or applicable codes for specific information regarding the spacing and 
placement of smoke detectors.
FIGURE 1: ALARM LOCATION DIAGRAM FOR RESIDENTIAL APPLICATION
 