2, Specification 
Equipment compatibility 
Heat pump system: 
3 heating stages: Y1, Y2 and W1 (auxiliary heating) 
2 cooling stages: Y1 and Y2 
Emergency heating: W1 
Reverse valve type O or B selectable 
Emergency heating HE/HG type selectable 
Heat pump fault feedback (L) indication 
Non heat pump system: 
2 heating stages: W1 and W2 
2 cooling stages: Y1 and Y2 
HE/HG selectable 
Jumper for separated heating and cooling circuit 
 
Terminals 
Number of terminals: 
9 + 1 (reserved for future) 
Terminals for heat pump 
Y1, Y2, W1, G, O/B, L, Rc, C 
Terminals for non heat pump 
Y1, Y2, W1, W2, G, Rc, Rh, C 
 
User interface 
Display: 
Segmented type LCD with blue backlight 
Input: 
Capacitive type “Touch Dial” 
Button: 
Hidden reset key 
 
Clock and Calendar 
Clock synchronization: 
via Internet. 
Clock free run accuracy: 
+/-2 seconds per day . 
Time display format: 
AM/PM / 24 hours format user selectable. 
DST: 
Enable / Disable user selectable. Clock automatically adjusted if DST is enabled. 
Time zone: 
-2 to +3 hours user selectable. 
Calendar: 
Valid through 2000 to 2099 
Calendar display format: 
MM-DD-YY. (Calendar is not displayed on home screen) 
 
Temperature Measurement 
Temperature display format: 
Fahrenheit or Celsius user selectable. 
Temperature display range: 
Fahrenheit: 32°F ~ 99°F, 1°F display resolution 
Celsius: 0°C ~ 40°C, 1°C display resolution 
Temperature measurement accuracy:  +/-0.5°C (15°C to 25°C room temperature) 
+/-1.0°C (full temperature measurement range) 
Calibration: 
Yes, via software, user adjustable. 
+/-7°F in 1°F resolution. 
+/-4°C in 0.5°C resolution.