4.6 
Cable Requirements 
Power supply cables wired to the input of a circuit breaker must be rated with respect to 
the previous  circuit breaker or fuse from which they were derived. Adequate current de-
rating should be applied to the cable as per the manufacturer’s instructions.  
4.7 
Hierarchy for Supply 
Figure 8 shows a typical wiring hierarchy for the equipment power supply cabling. 
Notice that the cable ratings are higher than the circuit breakers and fuse ratings. In this 
example  the  circuit  breaker  rating  has  been  de-rated  to  70%  of  the  cable  maximum 
continuous current rating. 
Also  note  that  the  current  rating  of  the  input  side  of  the  circuit  breaker  from  the  vehicle 
bus bar. This cable must be rated to exceed the current rating of the bus bar. In this case 
70% de-rating has been applied. 
VEHICLE BUS BAR (100A FUSED)
40A
CIRCUIT 
BREAKER
CP6100
5A
CIRCUIT 
BREAKER
JUNCTION 
BOX
5
A
 R
a
te
d
 C
a
b
le
5
7
A
 R
A
T
E
D
A
B
L
E
57A RATED CABLE
1
4
3
A
 R
A
T
E
D
A
B
L
E
LEGACY 
EQUIPMENT
LEGACY
RELAY
ANCILLAR
Y
CIRCUIT 
BREAKER
LEGACY
CIRCUIT 
BREAKER
ON/OFF
CONTROL
 
Figure 8: Typical Bus Power Supply Circuit Breaker and Cable Rating 
4.8 
Hot Plugging 
WARNING:
 
 
It is strongly recommended that power is turned off before the power is plugged in or out.  
!
Attention