COMBUSTION OF KODAK FILM, RESIN-COATED
PHOTOGRAPHIC PAPERS, AND PRINT AND DISPLAY MATERIAL
Refer to Current Information Summary, CIS-37 which is available
on our website:
http://www.kodak.com/eknec/documents/d2/0900688a80295
fd2/KES_CIS37ENG.pdf
Kodak's CIS 37 refers to NFPA 101, titled Life Safety Code. This Life
Safety Code mentions two NFPA standards, NFPA 701, and NFPA
255. We believe NFPA 255 is applicable to our display materials.
A fire test is done according to NFPA 255, using a test method
known as ASTM E 84 (ASTM E 84, ANSI/NFPA 255, UL 723,
and UBC No. 8-1 are comparable and identical in many respects).
NFPA = National Fire Protection Association
ASTM = American Society for Testing and Materials
ANSI = American National Standards Institute
UBC = Uniform Building Code
Most fire authorities ask for ASTM E 84 test results. The ASTM E
84 is a special test using a sample length of 22 feet (6.7 m), in a
tunnel-like test chamber. This is basically a fire-test-response
standard for the comparative burning behavior of building materials
and is applicable to exposed surfaces such as walls and ceilings.
The ASTM E 84 test results for ENDURA Transparency and Clear
Display materials are as follows:
Flame Spread Index (FSI) = 10
Smoke Developed Index (SDI) = 70
Overall Test Classification = A
The ASTM E 84 test results for our ENDURA Papers are as follows:
Flame Spread Index (FSI) = 40
Smoke Developed Index (SDI) = 10
Overall Test Classification = B
To explain the significance of the above, the lower the FSI, the
better the surface flame spread characteristics of the material.
If the FSI is 25 or less, the material is classified A.
If the FSI is between 26 and 75, the material classification is B.
If the FSI is 76 and above, the classification is C.
For any material, the Smoke Developed Index must be < 400.
The Life Safety Code NFPA 101 provides guidance on various
building occupancies and locations and the required classification
for a material in a given occupancy (such as mercantile) and
location (such as exit or corridor). Simply put, Class A is the most
desirable and has few use restrictions.