HP 380p Gen8 670857-S01 ユーザーズマニュアル

製品コード
670857-S01
ページ / 57
System Unit
System Unit
System Unit
System Unit
Dimensions
Dimensions
Dimensions
Dimensions (H x W x D)
(with bezel)
SFF Drives: 3.44 x 17.54 x 27.50 in (8.73 x 44.55 x 69.85 cm)
LFF Drives: 3.44 x 17.54 x 29.50 in (8.73 x 44.55 x 74.93 cm)
Weight
Weight
Weight
Weight (approximate)
Maximum
(all LFF hard drives, power
supply, and processor
installed)
61.00 lb (27.66 kg)
Minimum
(one SFF hard drive,
power supply, and
processor installed, ODD
not installed)
41.0 lb (18.59 kg)
Input Requirements
Input Requirements
Input Requirements
Input Requirements
(per power supply)
Rated Line Voltage
100 to 120 VAC
200 to 240 VAC
Rated Input Current
For 1200 W Power Supply:
10 A (at 100 VAC),
4.9 A (at 200 VAC)
For 750 W Power Supply:
8.9 A (at 100 VAC),
4.3 A (at 200 VAC)
For 460 W Power Supply:
5.5 A (at 100 VAC),
2.6 A (at 200 VAC)
Rated Input Frequency
50 to 60 Hz
Rated Input Power
For 1200 W Power Supply:
930 W (at 100 VAC),
1348 W (at 200 VAC)
For 750 W Power Supply:
857 W (at 100 VAC),
824 W (at 200 VAC)
For 460 W Power Supply:
526 W (at 100 VAC),
505 W (at 200 VAC)
BTU Rating
BTU Rating
BTU Rating
BTU Rating
Maximum
For 1200 W Power Supply:
3530 BTU/hr (at 100 VAC),
4600 BTU/hr (at 200 VAC)
For 750 W Power Supply:
2925 BTU/hr (at 100 VAC),
2812 BTU/hr (at 200 VAC)
For 460 W Power Supply:
1794 BTU/hr (at 100 VAC),
1725 BTU/hr (at 200 VAC)
Power Supply Output
Power Supply Output
Power Supply Output
Power Supply Output
(per power supply)
Rated Steady-State Power For 1200 W Power Supply:
800 W (at 100 VAC),
900 W (at 120 VAC),
1200 W (at 200 to 240 VAC)
For 750 W Power Supply:
750 W (at 100 to 120 VAC),
750 W (at 200 to 240 VAC)
For 460 W Power Supply:
QuickSpecs
HP ProLiant DL380p Generation8 (Gen8)
HP ProLiant DL380p Generation8 (Gen8)
HP ProLiant DL380p Generation8 (Gen8)
HP ProLiant DL380p Generation8 (Gen8)
Technical Specifications
DA - 14212   North America — Version 9 — April 12, 2012
Page 51