3.Protections
3.1 Over Voltage Protection --- Standard On +3.3V Output Set At 4.10Vdc At +/-0.40Vdc.
+5.0V Output Set At 6.25Vdc At +/-0.75Vdc.
+5.0V Output Set At 6.25Vdc At +/-0.75Vdc.
+12.0V Output Set At 14.6Vdc At +/-1.0Vdc.
3.2 Short Circuit Protection --- A Short Circuit Placed Between Dc Return And Output
Shall Cause No Damage And The Power Supply Shall Shutdown.
3.3 Over Power Protection --- The Power Supply Can Use Electronic Circuit To Limit The
Output. Power Against Excessing +150% Of Full Load. Or Protected against
Excessive Power Delivery Due To Short Circuit Of Any Output Or Over Total Power.
Excessive Power Delivery Due To Short Circuit Of Any Output Or Over Total Power.
3.4 No load Operation --- No Parts Damaged On Power Supply.
4.Dielectric Withstand Voltage
4.1 Primary to Secondary --- 1500Vac For 1 Minute. Or 1800Vac For 1 Sec.
4.2 Primary to Safety Ground --- 1500Vac For 1 Minute. Or 1800Vac For 1 Sec.
4.3 Insulation Resistance --- Primary To Safety Ground - 500Vdc, 50M ohms Min.
4.Environment
4.1 Operation Temperature -------------------- Air Temperature 0
qC
To 50
qC.
4.2 Operation Relative Humidity ------------- 20% To 90%.
4.3 Storage Temperature ----------------------- Air Temperature -20
qC
To 60
qC.
4.4 Storage Relative Humidity ---------------- 5% To 95%.
4.5 Altitude ----------------------------------------- Operate Properly At Any Altitude Between
0 To 100,000 Feet. Storage 40,000 Feet.
0 To 100,000 Feet. Storage 40,000 Feet.
4.6 Vibration --------------------------------------- 0.38mm. 5-55-5Hz, 1 Minutes Per Cycle;
30 Minutes For Each Axis ( X,Y,Z ).
30 Minutes For Each Axis ( X,Y,Z ).
5.Burn-In
5.1 Burn-In ------------------------------------------ At 45
q
C, Max. Load, 4 Hours.
6.Mean Time Between Failure
--------------------- 150 KHrs Minimum At Full Load For
25
qC Ambient Temperature.