Toshiba VF-AS1 ユーザーズマニュアル

ページ / 326
!
  E6581301!
G-13 
7.3.3  Setup  by  analog  input  signals  (RX  terminal)
Connect voltage signal (0 to ±10Vdc) to the terminal RX so that the inverter can be run and stopped with external 
commands. 
Title 
Function 
Adjustment range 
Default setting 
Example of setting
EOQF Command mode selection 
~
 (Terminal) 
 (Terminal) 
HOQF
Frequency setting mode 
selection 1 
~
 (RR/S4) 
 (RX) 
HOUN FM terminal meter selection 
~
HO
FM terminal meter adjustment 
H Frequency priority selection 
H Analog input filter 
 (No filter)~ (Max. filter) 
H RX input point 1 setting 
-~ % 
H RX input point 1 frequency 
~HJ Hz 
H RX input point 2 setting 
-~ % 
H RX input point 2 frequency 
~HJ Hz
*1
*1
*1: Inverter with a model number ending with    -WN, HN: 60.0    -WP: 50.0 
«An example of the connection of terminals: SW1 set to sink logic» 
„
Run/stop setup   
Run/stop operation by means of external 
commands. 
„
Setup of frequency setting signal and 
running frequency characteristic 
To set up frequency setting signal to be 
input to the external signal (RX terminal) 
and characteristic of running frequency.
Frequency characteristic is set up at the 
two points of RX reference point 1 
(H)/frequency (H), RX 
reference point 2 (H)/frequency 
(H). 
„
Connection and calibration of 
frequency meter
Connect a 1mAdc full-scale DC current 
meter, 7.5Vdc full-scale DC voltmeter or 
rectifier type AC voltmeter. 
For calibration of the meter, refer to the 
Section 5.16.
Run/Stop
-10~+10Vdc
H
!
H
!
H
!
H
Point 2 
Point 1 
Frequency setting signal
! -100%! ! ! !         0%! ! ! ! 100% 
  (-10V! !     ~!           0V  !     ~  ! +10V)
Operation frequency Hz
↑ 
Forward 
run 
Reverse 
run 
↓ 
*: Regardless of open/closed circuit between R and CC terminals, run and stop operation is 
controllable. 
Switching between forward run and reverse run is controllable by the terminals F/R and 
RX if reverse run prohibition selection H is properly set up. 
Ÿ
For details, refer to Section 6.14.4.
Motor
R/L1
U/T1
MCCB
Power 
supply 
S/L2
T/L3
V/T2
W/T3
CCA RX
RES
S1
S2
CC
S3
F
R
ST 
FM
AM
FLA
FLB
FLC
P24/PLC
OUT1
OUT2
VI/II
PP
VF-AS1 
CHARGE
Frequency 
meter 
NO 
CC
!
RR/S4 
IM