10. Selection of peripheral devices 
          Warning 
Mandatory 
• When using the inverter without the front cover, be sure to place the inverter unit inside a cabinet. If 
they are used outside the cabinet, it may cause electric shock. 
Be Grounded 
• Be sure to ground every unit. If not, it may cause electric shock or fire on the occasion of failure, 
short-circuit or electric leak. 
10.1 
 Selection of wiring materials and devices
!
Voltage
class
Applicable 
motor 
  [kW] 
Inverter model
Wire size 
!
Main circuit
DC terminal 
Braking resistor/
Braking unit 
(optional) (*4)
Earth cable 
Input terminal
(R, S, T)
Output terminal 
(U, V, W)
AWG
(*5) 
mm
2
(*6) 
AWG
(*5) 
mm
2
(*6) 
AWG 
(*5) 
mm
2
(*6)
AWG
(*5) 
mm
2
(*6)
AWG 
(*5) 
mm
2
(*7)
200V
class
0.4
VFAS1-2004PL
14
1.5
14
1.5
14
1.5
14
1.5
14
2.5
0.75
VFAS1-2007PL
14
1.5
14
1.5
14
1.5
14
1.5
14
2.5
1.5
VFAS1-2015PL
14
1.5
14
1.5
12
1.5
14
1.5
14
2.5
2.2
VFAS1-2022PL
12
1.5
12
1.5
10
2.5
14
1.5
14
2.5
3.7/4.0
VFAS1-2037PL
10
4
10
4
8
6
14
1.5
12
4
5.5
VFAS1-2055PL
8
6
8
6
6
10
14
1.5
10
6
7.5
VFAS1-2075PL
8
10
8
10
4
16
12
2.5
10
10
11
VFAS1-2110PM
4
16
4
16
3
16
10
4
10
16
15
VFAS1-2150PM
4
25
4
25
1
25
8
6
10
16
18.5
VFAS1-2185PM
3
25
3
25
1/0
35
8
10
8
16
22
VFAS1-2220PM
2
25
2
25
2/0
35
6
16
8
16
30
VFAS1-2300PM
2/0
50
2/0
50
4/0
70
4
25
6
25
37
VFAS1-2370PM
3/0
70
3/0
70
250MCM
95
3
35
6
35
45
VFAS1-2450PM
4/0
70
4/0
70
300MCM
95
2
50
6
35
55
VFAS1-2550P
3/0×2
70×2
3/0×2
120
4/0×2
95×2
1/0
50
2
70
75
VFAS1-2750P
4/0×2
95×2
250MCM×2
70×2
300MCM×2 120×2
1/0
35×2
2
95
400V
class
0.75
VFAS1-4007PL
14
1.5
14
1.5
14
1.5
14
1.5
14
2.5
1.5
VFAS1-4015PL
14
1.5
14
1.5
14
1.5
14
1.5
14
2.5
2.2
VFAS1-4022PL
14
1.5
14
1.5
14
1.5
14
1.5
14
2.5
3.7/4.0
VFAS1-4037PL
12
1.5
12
1.5
10
2.5
14
1.5
14
2.5
5.5
VFAS1-4055PL
10
2.5
10
2.5
8
4
14
1.5
12
2.5
7.5
VFAS1-4075PL
10
4
10
4
8
6
14
1.5
12
4
11
VFAS1-4110PL
8
6
8
6
6
10
14
1.5
10
6
15
VFAS1-4150PL
6
10
6
10
4
16
12
2.5
10
10
18.5
VFAS1-4185PL
6
10
6
10
4
16
10
2.5
10
10
22
VFAS1-4220PL
6
10
6
10
4
16
10
4
10
10
30
VFAS1-4300PL
4
16
4
16
2
25
8
6
10
16
37
VFAS1-4370PL
3
25
3
25
1
35
8
10
8
16
45
VFAS1-4450PL
1
35
1
35
2/0
50
6
16
8
16
55
VFAS1-4550PL
1/0
50
1/0
50
3/0
70
6
16
6
25
75
VFAS1-4750PL
3/0
70
3/0
70
250MCM
95
3
35
6
35
90
VFAS1-4900PC
1/0×2
70×2
1/0×2
95
1/0×2
95×2
1/0
35
2
70
110
VFAS1-4110KPC
3/0×2
95×2
3/0×2
120
2/0×2
120×2
1/0
50
2
95
132
VFAS1-4132KPC
4/0×2
95×2
4/0×2
150
4/0×2
120×2
4/0
70
1/0
95
160
VFAS1-4160KPC 300MCM×2
120×2
300MCM×2
95×2
350MCM×2
150×2
4/0
95
1/0
120
200
VFAS1-4200KPC
4/0×3
150×2
4/0×3
120×2
3/0×3
150×3
300MCM
150
1/0
150
220
VFAS1-4220KPC 250MCM×3
150×3
250MCM×3 120×2
4/0×3
150×3
300MCM
150
2/0
150
280
VFAS1-4280KPC 350MCM×3
150×3
350MCM×3 185×2
300MCM×3
150×4
300MCM
150
3/0
120×2
355 
VFAS1-4355KPC
400MCM
×2×2 (*9,10)
120×2×2
(*9,10)
400MCM×4
(*10)
150×3
500MCM×3 185×4 350MCM×2 185×2
4/0 
120×2
400 
VFAS1-4400KPC
500MCM
×2×2 (*9,10)
150×2×2
(*9,10)
500MCM×4
(*10)
185×3
500MCM×4
185×4
(*8)
350MCM×2 185×2
4/0 
150×2
500 
VFAS1-4500KPC
400MCM
×3×2 (*9,10"
150×3×2
(*9,10)
400MCM×5
(*10)
185×4
(*10)
500MCM×4
180×4
(*8)
350MCM×2 185×2 250MCM 150×2
(*1): The recommended cable size is that of the cable (e.g. 600V class, HIV cable) with continuous maximum permissible temperature of 75°C. Ambient 
temperature is 40°C or less and the wiring distance  is 30m or less. 
(*2): For the control circuit, use shielded wires whose size (cross-section) is 0.75 mm
2
 or more.   
(*3): For the earth cable, use wires larger than the specified ones in size (cross-section). 
(*4): Recommended wire size for an optional braking resistor. Refer to 5.19 for use of external braking resistor. 
(*5): This cable size is conformity to UL508C. 
(*6): This cable size is conformity to IEC60364-5-52. 
(*7): This cable size is conformity to IEC60364-5-54. 
(*8): The recommended cable is 600V class HIV cable with permissible temperature of 90°C. 
(*9): The number refers to a cable composition. For example, in the case of “120×2×2”: 120×2×2
Number of cables connected in parallel on the terminal board
Number of cables connected to each terminal board
Wire size 120mm