Toshiba VF-AS1 ユーザーズマニュアル

ページ / 326
!E6581301 
C-3 
3.2 
Simplified operation of the VF-AS1 
On of three operation modes can be selected: terminal board operation, operation panel and combination of both.   
Ÿ
 For other operation modes, refer to Section 5.5. 
Terminal board mode
   
:Operation by means of external signals 
Operation panel mode   
:Operation by pressing keys on the operation panel 
Operation panel + terminal board mode    :Frequency, start/stop signals can be 
sent individually from the operating panel and terminal board.
3.2.1  Terminal  board  operation
In this mode, the motor is started or stopped according to the ON/OFF signal to input terminals (such as the ST 
terminal and the F terminal). Also, the frequency is set according to the potentiometer/voltage/current signals to 
analog input terminals (such as the RR/S4 terminal, VI/II terminal and RX terminal). 
Ÿ
 For more details, refer to Section 7. 
 Example of standard connection
 
Motor
IM
CCA
RX VI/II RR/S4 PP 
F
R
CC 
R/L1 
U/T1 
External potentiometer (or voltage signal RR/S4-CCA:0 to 10Vdc) 
Voltage signal:-10~+10Vdc
Voltage signal:0~10Vdc 
or current signal:4(0)~20mAdc
ON:Forward run, OFF:Deceleration stop 
Stand-by:ON:Stand-by, OFF:Coast stop
ST
ON:Reverse run, OFF:Deceleration stop 
V/T2 
W/T3
S/L2 
T/L3 
Power 
supply
MCCB
Inverter
■ Run/Deceleration stop!!!! Selecting a command mode for basic parameters EOQF
EOQF
EOQF
EOQF=
 (standard default 
setting)
              and               
are connected: Forward run
              and               
are disconnected: Deceleration stop 
(When terminals              and                are electrically connected) 
F
CC
F
CC
CC
ST
!
Frequency
ON 
OFF
ON 
OFF
F-CC 
Deceleration!
ST-CC 
"!
For  coast  stop 
Open the connection between ST and CC 
when stopping the motor in the state 
described at left. The monitor on the inverter 
at this time will display QHH.   
Motor 
speed
ON 
OFF
ON 
OFF
F-CC
ST-CC
Coast  stop