Reliance Water Heaters RUF 100 199 SERIES 100 ユーザーズマニュアル

ページ / 36
13
 WARNING
THE HEATER IS NOT INTENDED FOR OPERATION AT HIGHER THAN 
10.5" (2.59 KPa) WATER COLUMN SUPPLY GAS PRESSURE. HIGHER  
GAS SUPPLY PRESSURES REQUIRE SUPPLEMENTAL REDUCING 
SERVICE  REGULATION.  EXPOSURE  TO  HIGHER  GAS  SUPPLY 
PRESSURE MAY CAUSE DAMAGE TO THE GAS CONTROLS WHICH 
COULD RESULT IN FIRE OR EXPLOSION. IF OVERPRESSURE HAS 
OCCURRED  SUCH  AS  THROUGH  IMPROPER  TESTING  OF  GAS 
LINES OR EMERGENCY MALFUNCTION OF THE SUPPLY SYSTEM 
THE GAS VALVE MUST BE CHECKED FOR SAFE OPERATION. MAKE 
SURE THAT THE OUTSIDE VENTS ON THE SUPPLY REGULATORS 
AND  THE  SAFETY  VENT  VALVES  ARE  PROTECTED  AGAINST 
BLOCKAGE.  THESE  ARE  PARTS  OF  THE  GAS  SUPPLY  SYSTEM, 
NOT  THE  HEATER.  VENT  BLOCKAGE  MAY  OCCUR  DURING  ICE 
STORMS.
IT IS IMPORTANT TO GUARD AGAINST GAS VALVE FOULING FROM 
CONTAMINANTS  IN  THE  GAS  WAYS.  SUCH  FOULING  MAY  CAUSE 
IMPROPER OPERATION, FIRE OR EXPLOSION. 
IF COPPER SUPPLY LINES ARE USED THEY MUST BE INTERNALLY 
TINNED AND CERTIFIED FOR GAS SERVICE.
BEFORE ATTACHING THE GAS LINE BE SURE THAT ALL GAS PIPE IS 
CLEAN ON THE INSIDE.
TO TRAP ANY DIRT OR FOREIGN MATERIAL IN THE GAS SUPPLY 
LINE, A DIRT LEG (SOMETIMES CALLED A SEDIMENT TRAP OR DRIP 
LEG)  MUST  BE  INCORPORATED  IN  THE  PIPING  (SEE  FIGURE  13). 
THE DIRT LEG MUST BE READILY ACCESSIBLE AND NOT SUBJECT 
TO  FREEZING  CONDITIONS.  INSTALL  IN  ACCORDANCE  WITH 
RECOMMENDATIONS OF SERVING GAS SUPPLIERS. REFER TO THE 
NATIONAL FUEL GAS CODE.
FIGURE 13.
CONNECTION OF GAS PIPE
1.  When connecting gas pipe to unit, apply wrench to flange only. Note:  
Do not use wrench on gas valve or gas bracket.  See Figure 14.
2.  PERFORM THE GAS LEAK TEST ANY TIME WORK IS DONE ON A GAS 
SYSTEM TO AVOID THE POSSIBILITY OF FIRE OR EXPLOSION WITH 
PROPERTY DAMAGE, PERSONAL INJURY OR LOSS OF LIFE.
FIGURE 14.
The Gas Leak Test is performed as follows:  Paint pipe connections upstream 
of gas control with a rich soap and water solution to test for leaks before 
operating main burner. Bubbles indicate gas leak. To stop leak, tighten pipe 
connections. After piping connections are checked, turn on main burner. With 
main burner in operation, paint pipe joints (including flanges), pilot gas tubing 
connections and control inlet and outlet with rich soap and water solution. 
Bubbles indicate gas leak. To stop leak, tighten flange screws, joints and 
pipe connections. Replace part if leak can’t be stopped.
To prevent damage, care must be taken not to apply too much torque when 
attaching gas supply pipe to gas valve inlet. 
Apply joint compounds (pipe dope) sparingly and only to the male threads of 
pipe joints. Do not apply compound to the first two threads. Use compounds 
resistant to the action of liquefied petroleum gases.