Emerson PowerSure Interactive 2 1440VA PS1440RT2-230 ユーザーズマニュアル

製品コード
PS1440RT2-230
ページ / 4
Liebert HIROSS UPS Headquarters
Via Gioacchino Rossini,6
20098 - S.Giuliano Milanese (MI)
tel. +39 02 982501  fax +39 02 98250337
www-liebert-hiross.com
info.ups@liebert-hiross.com
Liebert HIROSS Services Headquarters
Via Leonardo da Vinci,8
35028 - Piove di Sacco (PD)
tel. +39.049 9719111  fax +39 049 9717053
service@liebert-hiross.com
Emerson Network Power Ltd - UK
Fourth Avenue, Globe Park - Marlow
Buckinghamshire - SL71YG
tel. +44 1628 403200  fax +44 1628 403203
BR
O
-PS
I2@-GB
-XX/01-04/C
o
n
te+Oggioni+P
ar
tne
rs/Prin
ted in It
aly
ISO9000
CERTIFIED
COMPANY
While every precaution has been taken to ensure accuracy and completeness in this brochure, Liebert HIROSS assumes no responsibility, and disclaims all liability for damages resulting from use of  this information
or for any errors or omissions. All rights reserved throughout the world. Specifications subject to change without notice. All names referred to are trademarks or registered trademarks of their respective owners.
The Emerson logo is a Trademark and a service mark of emerson eletric co.
Technical Data [PowerSure PSI] 
Model PS1000RT2-230
PS1440RT2-230
PS2200RT2-230E
PS3000RT2-230E
Power Rating 
VA
1000
1440
2200
3000
W
750
1080
1650
2250
Dimensions
Unit  (WxDxH mm)
87 (2U) x 557 x 430
87 (2U) x 557 x 430
87 (2U) x 612 x 430
87 (2U) x 612 x 430
Shipping  (WxDxH mm)
300 x 706 x 598
300 x 706 x 598
333 x 864 x 598
333 x 864 x 598
Weight
Unit (kg)
28
31
35
37
Shipping (kg)
36.6
39
43.6
45.6
Input Parameters
Surge Protection
660J
Voltage Range w/o Battery Operation 
155-291 VAC
Dip switch selectable 220-230-240V
Frequency Range
45-65Hz (±0.1)
Input Power Connection
1 IEC-320-C14
1 IEC-320-C20
Output Parameters
Output Receptacles
8 IEC-320-C13
8 IEC-320-C13 + 
1 IEC-320-C19
Output Power Cables
2 m detached IEC-320-C14 
Voltage (Normal Mode) 
220-230-240VAC ±10%
Voltage (Battery Mode) 
230VAC ±8%
Waveform (Battery mode)
Sinewave
Frequency
50 or 60Hz (auto-sensing)
Overload warning 
>100%  (Normal and Battery Mode)
Overload Shutdown  
>200% - shortcircuit; after 15 cycles (normal mode)
Battery Parameters
Type - Approved manufacturers
Valve-regulated, non-spillable, lead acid - B&B Batteries, CSB, Panasonic, Enersys
Quantity x Voltage x Rating
4 x 12 V x 7Ah
4 x 12 V x 7Ah
6 x 12 V x 7Ah
6 x 12 V x 9Ah
Transfer time
4-6ms typical
Backup Time
At 25°C resistive loading with fully charged batteries
Full load (minutes)
11
5
5
6
Half load (minutes)
26
16
16
16
Recharge time
6 Hours to 90% capacity, after full discharge into a resistive load
Battery test
Every 14 days 
Hot Swap Batteries
Yes
Deep discharge protection
Yes
Black start (w/o mains)
Yes
Environmental
Noise
< 40dB normal mode operation
Operating temperature
0°C to +40°C for altitude 0 to 1500 meter above sea level
0°C to +30°C for altitude 1500 to 3000 meter above sea level
Operating Altitude
Up to 2000m without derating
Up to 3000m without derating
Comunications
USB, Serial RS232, Contact Closure, Web and SNMP (optional card) 
USB Compatibility
Windows 2000, Windows XP, Apple Mac OS
Software Compatibility
MultiLink 3.0 supports MS Windows NT/2000/XP/95/98/ME, AIX, Linux, Sun Solaris, HP-UX, Novell Netware
Package
Multi-language, Multi-page User Manual - MultiLink 3.0 CD or later - One (1) DB9 Serial Cable
One (1) RJ11 modem cable - One (1) USB Cable - Two (2) 10A 2.0 meter output power cord 
Rack mount handles, Support base for Tower configuration, Extensible Fixed Rack Mount rails (20.5" - 31") 2200, 
3000VA models only: (1) Schucko CEE 7/7 to IEC-320-C19 and (1) BS1363 to IEC-320-C19, 16A input power cord
Warranty
2 Years
Standards & Requirements
Safety
EN 62040-1-1;  CE low voltage directive;  TUV Certificate
EMI / EMC
EN 50091-2, Class B;  CE EMC directive
Design
Line Interactive IEC62040-3 VI, EN61000-3, EN61000-4, EN60950
Battery Cabinets
Extensible Batteries
PS2-48VBATT
PS2-72VBATT
Unit  (WxDxH mm)
87 x 557 x 430
87 x 612 x 430
Shipping  (WxDxH mm)
300 x 706 x 598
333 x 864 x 598
Weight
Unit (kg)
30
46
Shipping (kg)
38.6
53.6
Quantity x Voltage x Rating
2 by 4 x 12V x 7Ah
2 by 6 x 12V x 9Ah
Approved Manufacturers
CSB, B&B, Enersys
Battery cabinet package
(1) Battery Cable, Tower stand support base, Rack mount handles and fixed rail kits
Extended Backup time
1 Cabinet (full/half load)
46/119
30/72
40/99
29/67
2 Cabinets (full/half load)
98/209
56/133
77/150
52/129
3 Cabinets (full/half load)
136/274
95/209
120/222
88/168
4 Cabinets (full/half load)
188/305
125/257
144/274
118/222
Approximate discharge times are in minutes and at 25°C with resistive load.